92
FCP-75 Manual —
P/N LS10147-003FK-E:A 3/17/2021
Programming
Point
9.5.3 Point Programming For FIK-5880 and FIK-5865 Modules
To program for a FIK-5880 or FIK-5865 module points, follow these steps:
1.
Enter the Installer Code.
2.
Select 7 for Program Menu.
3.
Press 4 to enter the Point Menu.
4.
Press the up or down arrows to select the desired module. Refer to Section 8.5 for available choices. Press ENTER.
Figure 9.6 Programming Points Screen for FIK-5880 and FIK-5865 Modules
5.
Enter the Point Number, then press ENTER.
Choices
Type Selections
Function Selections
for each Type
Comments
Enter Point or Circuit
Select Type
UNUSED
NOTIF OUT
CTRL CKT
AUX PWR
CONSTANT
Constant auxiliary power.
RESETTABLE
Resettable auxiliary power.
DOOR
Door holder auxiliary power.
AUX SYNC
Sounder Sync auxiliary power for System Sensor
B SWITCH*
MAN PULL
Refer to comments column of
Table 9.4 for description of these options
Latch or Non-latching feature only appears for waterflow, supervisory,
tamper, zone aux1, zone aux2, system aux1, and system aux2
WATERFLOW
SUPERVSY
TAMPER
FIRE DRILL
SILENCE
RESET
PAS_ACK
ZN_AUX1
ZN_AUX2
SYS_AUX1
SYS_AUX2
MAN REL
ILOCK
STATUS POINT
Non-latching - Used to activate an ancillary Output Group that does not
active alarm, sound PZT, display status or report events. Reset has no affect
on this point
A SWITCH*
Same as B SWITCH
B DETECTOR*
2-WIRE SMOKE
Used for Class B, 2-wire detectors.
4-WIRE SMOKE
Used for Class B, 4-wire detectors.
CO 4-WIRE DET
Used for Class B, 4-wire CO detectors.
CO 4-WIRE SUP DET
Latching or Non-latching used for Class B, 4-wire CO Supervisory detectors
A DETECTOR*
2-WIRE SMOKE
Used for Class A, 2-wire detectors.
4-WIRE SMOKE
Used for Class A, 4-wire detectors.
CO 4-WIRE DET
Used for Class A, 4-wire CO detectors.
CO 4-WIRE SUP DET
Latching or Non-latching used for Class A, 4-wire CO Supervisory detectors
Select Group
Group or Zone selection will appear depending on the type selected
Edit Name
Edit name. See Section 9.5.2
*Only applicable on FIK-RPS1000
Table 9.5 Menu choices for Internal/External Power Modules