Point
Programming
FCP-75 Manual —
P/N:LS10147-003FK-E:A 3/17/2021
91
9.5.2 Point Programming for the Internal or External Power Module
To program for an internal or external power module points, follow these steps:
1.
Enter the Installer Code.
2.
Select 7 for the Program Menu.
3.
Press 4 to enter the Point Menu.
4.
Press the up or down arrows to select the desired module. Press ENTER.
Refer to Section 8.5 for the available choices.
5.
Enter the number of the circuit or point you want to edit. Refer to Table 9.5 for available selections.
6.
Press ENTER.
7.
To select the Type, press the up or down arrows, then press ENTER.
8.
To select the Function, press the up or down arrows, then press ENTER.
9.
To select the Group, press the up or down arrows, then press ENTER.
10. To edit the Point Name, press the right arrow to skip point name edit. See Section 9.5.
11. Repeat Steps 1 through 10 for all circuits.
NOTIF
OUTPUT PT
Select Group
Output Point, a general use notification type. Use for driving standard notification
appliances.
AUX CONST
Use constant power for applications that require a constant auxiliary power
source. Power is always present at Constant circuits.
AUX RESET
Use for auxiliary power, resettable applications. See “Resettable Power” on
page 45 to learn how this option operates.
AUX DOOR
Use for auxiliary power, door holder applications. For example, if you were using
an auxiliary power supply for door holders, you would use this option. See “Door
Holder Power” on page 44 to learn how this option operates.
RELAY
OUTPUT PT
Select Group
Output Point, a general use relay type. Use for applications requiring a relay, such
as elevator recall.
AUX RESET
Use for auxiliary power, resettable applications. See “Resettable Power” on
page 45 to learn how this option operates.
AUX DOOR
Use for auxiliary power, door holder applications. For example, if you were using
an auxiliary power supply for door holders, you would use this option. See “Door
Holder Power” on page 44 for a description of how this option operates.
Type
Selection
Function
Latching Option
Comments
Table 9.4 Point Programming for Internal SLC Module (Continued)