System Options
Programming
FCP-75 Manual —
P/N:LS10147-003FK-E:A 3/17/2021
97
A screen similar to the one shown in Figure 9.13 will display.
Figure 9.13 Water Flow Delay Programming Screen
5.
Enter the number of seconds (0 to 90) to delay an a water flow switch alarm, then press ENTER.
Alarm Verify
You can set the alarm verification time from 60 to 250 seconds (default is 60 seconds).
To set the alarm verification:
6.
Enter the desired number of seconds for the alarm verification time.
7.
Press the right arrow or ENTER to make your selection and move to the next programming option.
AC Report Delay
You can adjust the number of hours before a Low AC report will be sent to the central station.
To program low AC report delay, follow these steps:.
Figure 9.14 Low AC Report Delay Programming Screen
8.
Enter the number of hours before a low AC report will be sent to the central station, then press ENTER.
AC Line Frequency
The panel’s AC line frequency is selectable for 60 Hz or Internal. AC Frequency feature dictates how the control panel will calculate time
based on the AC line frequency used in the installation site. The “Internal” option can be used in areas where the AC line frequency is not
dependable and you want the panel to calculate time from the internal crystal. The internal crystal is not as accurate as the AC power source
and 60 Hz should normally be selected. The panel defaults to the 60 Hz. selection.
To change the AC line frequency, continue programming from steps above:
9.
Select 60 or Intl, by pressing the up or down arrow, then press ENTER.
Clock Display Format (AM/PM or Military)
To change the system clock display format, continue programming from step 8 above:
10. Select AMPM (for AM/PM display format) or MIL (for military or 24 hr display format) by pressing the up or down arrow, then press
ENTER.
Auto-Resound (4 or 24 hours)
The system resound time period can be modified from the default value 24 hours to 4 hours. This setting adjusts when the FACP will auto-
matically resound events after being silenced. Set this option to 4 hours when using the SWIFT devices.
9.6.5 Miscellaneous Options
Through this programming option you can turn on or off strobe synchronization during silence, display status at Idle (auto display event),
report by zone or point, and single key acknowledge.
To edit miscellaneous options, do the following.
1.
Enter the Installer Code.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 5 for Miscellaneous Options.
Delay in seconds
before waterflow
alarm occurs.
(00 - 90)
NOTE:
You must select 1-3 hours in UL central station installations and UL remote signaling installations
Low AC Report delay
in hours (00-30)