APPENDIX A
UL S2203
Cheetah Xi 50 Installation Manual
A-3
FM
P/N: 06-369
Rev 6, 09/2015
Section 3 – Auxiliary Power
Item
Device Description
Standby
Current per
Unit (Amps)
Qty
Total
Standby
Current per
Unit (Amps)
Alarm
Current per
Unit (Amps)
Qty
Total Alarm
Current per
Unit (Amps)
1
68-140 FAAST
0.500
x
=
0.650
x
=
2
68-302 FAAST XT
0.500
x
=
0.650
x
=
3
55-052/053 RCM w/ Agent
0.0194
x
=
0.010
x
=
3a
10-1832 ARM
[Note 2]
0.002
x
=
0.008
x
=
3b
10-2748 IRM
[Note 2]
0.003
x
=
0.037
x
=
4
55-052/053 RCM w/ Solenoid
0.0364
x
=
0.010
x
=
4a
Releasing Solenoid Coil
[Note 3]
NA
x
NA
=
NA
x
=
5
55-042/047 SCM w/ Solenoid
[Note 3]
NA
x
NA
=
NA
x
=
6
10-2413 Master-box Supervisor
0.022
x
=
0.283
x
=
6a
Master-box Trip Coil
[Note 3]
NA
x
NA
=
NA
x
=
7
63-1064 Sounder Base
0.007
x
=
0.027
x
=
8
10-2528/-2476 DACT
0.150
x
=
0.190
x
=
9
10-2630 2-button RDU
0.036
x
=
0.139
x
=
10
10-2631 10-button RDU
0.036
x
=
0.139
x
=
11
10-2646 14-button RDU
0.036
x
=
0.139
x
=
12
10-2627 Ethernet Module
0.097
x
=
0.134
x
=
13
10-2583 Multi-Interface
0.200
x
=
0.200
x
=
14
10-2411 LED Graphic Micro
0.067
x
=
0.140
x
=
15
10-2667 20-Zone Remote Annun.
0.051
x
=
0.148
x
=
16
10-2785 Relay Card
[Note 5]
0.032
x
=
0.256
x
=
17
10-2777 Relay Assy.
[Note 4]
0.047
x
=
0.109
x
=
18
10-2204 CRM4 Relay
[Note 5]
0.011
x
=
0.040
x
=
19
10-2770 HPM4 Relay
[Note 5]
NA
x
NA
=
NA
0.086
x
=
20
10-2792 Class A Peripheral
0.057
x
=
0.057
x
=
21
10-2814 LOC Digital Paging
0.103
x
=
0.140
x
=
22
10-2616 Keltron Printer
0.200
x
=
1.200
x
=
23
10-2277 VESDA HLI
0.245
x
=
0.245
x
=
Total Aux. Power Standby
Current (Amps):
Total Aux. Power Alarm
Current (Amps):
Insert totals in Section 1 – Line Item 3.
Notes:
1.
Indicate the current draw of the devices in this section only if the 24vdc power for device operation is supplied by the Cheetah Xi 50 system
controller. Typical for all devices.
2.
Indicate quantity of ARMs or IRMs connected to the RCM.
3.
Indicate alarm current draw of the coil that is connected to the module.
4.
Assembly includes control card and relay bus card. Add the quantity of CRM4 and HPM4 relay cards installed on the bus card in rows 18 and
19.
5.
Current values shown assume all relays are active.