APPENDIX A
A-2
Cheetah Xi 50 Installation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-369
FM
Section 2 – Signaling Line Circuit
Item
Addressable Device Description
Standby
Current per
Unit (mA)
Qty
Total Standby
Current per
Unit (mA)
Alarm
Current per
Unit (mA)
Qty
Total Alarm
Current per
Unit (mA)
1
63-1052/1058 Photo
0.481
x
=
2.000
x
=
2
67-033/034 Ion
0.481
x
=
2.000
x
=
3
63-1053/1059 Photo/Heat
0.481
x
=
2.000
x
=
4
60-1039/1040 Heat
0.451
x
=
2.000
x
=
5
63-1057/63-1062 Photo/Duct
0.481
x
=
2.000
x
=
6
68-140 FAAST
[Note 1]
0.300
X
=
0.650
x
=
7
68-302 FAAST XT
[Note 1]
0.465
X
=
0.493
x
=
8
55-045/050 MMM
0.485
x
=
2.000
x
=
9
55-041/046 MM
0.485
x
=
2.000
x
=
10
20-1063/1064 Pull Station
0.370
x
=
2.000
x
=
11
20-1343 Release Pull Station
0.370
x
=
2.000
x
=
12
55-042/047 SCM
[Note 2]
0.630
x
=
2.000
x
=
13
55-043/048 RM
0.580
x
=
2.000
x
=
14
63-1063 Relay Base
0.170
x
=
0.170
x
=
15
55-052/053 RCM
[Note 3]
0.450
x
=
6.000
x
=
16
63-1064 Sounder Base
[Note 1]
0.300
x
=
0.300
x
=
17
02-3868 Remote Annunciator
NA
x
NA
=
NA
10.000
x
=
18
02-3869 Remote Test
NA
x
NA
=
NA
10.000
x
=
19
02-4998 Remote Key Test
NA
x
NA
=
NA
12.000
x
=
Total SLC Standby
Current (mA):
Total SLC Alarm
Current (mA):
Total SLC Standby (mA):
/1000 =
A
Total SLC Alarm (mA):
/1000 =
A
Total
Total
Insert totals in Section 1 – Line Item 2.
Notes:
1.
Device requires 24vdc power for operation. Include device current draw in Section 3.0 if power is supplied by the Cheetah Xi 50 system
controller.
2.
Device requires 24vdc power for operation of connected devices. If using the SCM to control the operation of master-box interface or sprinkler
solenoids, include current draw for all connected devices in Section 3.0. If using the SCM to control notification appliances, include current draw
for all connected devices in Section 4.0.
3.
Device requires 24vdc power for operation of connected releasing device(s). Include current draw for all connected devices in Section 3.0.
Summary of Contents for 10-071
Page 75: ......