4.0 INSTALLATION
4-18
Cheetah Xi 50 Installation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-369
FM
4.15 CONFIGURE SYSTEM
There are many different methods that can be chosen to configure the Cheetah Xi 50 fire alarm system. The
two most common choices would be to AUTO PROGRAM or ENGINEERED CONFIGURE. Any combination
of these two methods may also successfully accomplish matching the field devices to the installation
configuration requirements. Refer to Fike Document 06-657, “Cheetah Xi 50 Programming Manual” for
specific details on how to configure the system.
4.16 ACCEPTANCE TEST
Once the system has been wired, configured, and any faults corrected, all installed components should be
tested as a system to insure proper operation and to verify compliance with applicable NFPA standards.
Testing should be conducted by a factory-trained fire alarm technician in the presence of a representative of
the Authority Having Jurisdiction (AHJ) and the owner’s representative.
The initial system check is required to verify that all components of the system are installed and operating as
intended. Where test results differ from those expected, corrective action must be taken.
Before commencing testing, notify all areas where the alarm sounds and off-premises locations that receive
alarm and trouble transmissions that testing is in progress.
When the system has been tested and found to operate satisfactorily, a “Record of Completion” document ,
referenced in NFPA 72, shall be filled out and mounted near the fire alarm panel or provide it to the building
representative.
Records of all testing and maintenance shall be kept on the protected premises for a period of at least five (5)
years.
A complete check of installed field wiring and devices should be made at regular intervals, in accordance with
NFPA 72 requirements.
4.17 INSTALL THE DEAD-FRONT PANEL
The dead-front panel should not be installed until after all testing and system commissioning has been
completed. Refer to Fike document 06-647, “50-point Dead-Front Panel Installation Instructions”.
DEADFRONT
BOTTOM VIEW
FRONT VIEW
K5
K6
K7
JTAG
P10
24V
P5
P4
A
U
X
#1
F
4 4A
P3
P2
10-2620 REV
02-11544 REV A
F1
F2
F3
F6
F5
F4
P1
P2
P3
P4
S
W
1
E
TH
E
R
N
E
T
M
OD
U
L
E
P
/N
1
0-
2627
PANEL FRONT VIEW
WITH DEADFRONT PANEL
Exhibit 4-23: Dead-Front Panel
Summary of Contents for 10-071
Page 75: ......