3.0 SYSTEM COMPONENTS
3-20
Cheetah Xi 50 Installation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-369
FM
3.9.3
ADDRESSABLE PULL STATION, P/N 20-1063
ADDRESSABLE PULL STATION WITH ISOLATOR,
P/N 20-1064
The Addressable Pull Station (See Exhibit 3-40) is a non-coded,
dual-action manual pull station. A Mini Monitor Module is housed
inside the pull station to provide an alarm initiating input to the
control panel. The isolator version provides complete short circuit
isolation for NFPA Class X wiring.
3.9.4
SUPERVISED CONTROL MODULE, P/N 55-042
SUPERVISED CONTROL MODULE WITH ISOLATOR,
P/N 55-047
The Supervised Control Module (See Exhibit 3-41) is used to switch
an external power supply or audio amplifier to notification appliances.
The module monitors the external power input for loss of power and
signals the Cheetah Xi 50 panel accordingly. The module includes a
tri-color LED for instant indication of device status. The module is
capable of providing an optional pulsing output to signal different
states, when interfaced with the Cheetah Xi 50 addressable loop.
The isolator version provides complete short circuit isolation for
NFPA Class X wiring. A module cover plate (not shown) is included
with the module.
In addition to interfacing with notification appliances, the SCM can
also be used to operate either of the following interfaces:
3.9.4.1
SOLENOID PROTECTION ASSEMBLY, P/N 10-2360
The SCM can be connected to a single sprinkler solenoid rated up to
2 amps maximum at 24VDC. The Solenoid Protection Assembly
(See Exhibit 3-42)
must
be used when connecting a solenoid to the
SCM. Refer to Fike document 06-186 for compatible sprinkler
solenoids (Factory Mutual Approved Groups A-G).
Refer to Fike document 06-344 for more information.
Exhibit 3-41: Supervised
Control Module
Exhibit 3-42: Solenoid
Protection Assembly
Exhibit 3-40: Pull Station
Summary of Contents for 10-071
Page 75: ......