Chapter 4 Installation and Wiring
PAGE 4-15
As shown below, the output signal at each terminal takes on one of two definitions in accordance with the
combination with the BANK SELECT Input signal being either OFF or ON.
BANK SELECT
OFF
ON
TB2
-1
REJECT(NG)
WORK SELECT 5
OUT-1
TB2
-2
ACCEPT(OK)
CF WARNING*
OUT-2
TB2
-3
ABNORMAL
BATCH SEQ. END*
OUT-3
TB2
-4
READY
WORK SELECT 0
OUT-4
TB2
-5
BUSY
WORK SELECT 1
OUT-5
TB3
-7
RESULT DATA
WORK SELECT 2
OUT-6
TB3
-8
CF CARD FULL
WORK SELECT 3
OUT-7
TB2
-6
BYPASS
WORK SELECT 4
OUT-12
NG: FASTENING REJECT SIGNAL
PIN No.: TB2-1
OUT-1
Output when the fastening result falls outside programmed limits.
OK: FASTENING ACCEPT SIGNAL
PIN No.: TB2-2
OUT-2
Output when the fastening result is acceptable within the programmed limits.
ABNORMAL: SYSTEM ERROR / ABNORMAL
PIN No.: TB2-3
OUT-3
Output when a system fault / error is detected during a system check or during the fastening process.
When an error occurs, fastening is stopped immediately and the fastening results data is stored.
Normal process cannot begin until the problem is corrected and a RESET signal is input.
READY SIGNAL
PIN No.: TB2-4
OUT-4
Output when the system is in the READY condition. Indicates system is ready to operate and inputs
are enabled. This signal is inactive (off) in the following conditions:
•
During the initialization process when power is turned on (for approx.. 5 sec.)
•
STOP condition
•
While fastening is in process (when BUSY)
•
While Reset signal is on
•
Bypass condition
•
Abnormal condition
•
When a START or REVERSE signal is on
•
During a CAL check
•
When operation of the system by an external input is impossible
BUSY SIGNAL
PIN No.: TB2-5
OUT-5
Output when the controller is in cycle for a fastening process.
FASTENING RESULT DATA AVAILABLE SIGNAL
PIN No.: TB3-7
OUT-6
Output “ON” when the fastening results are available to be collected via the HFC software.
This signal turns
“OFF” after data collection has completed and can be used to monitor that the
HFC3000 software is monitoring / collecting data (when AFC3000 Software is used)
CF CARD FULL
PIN No.: TB3-8
OUT-7
Output when capacity of the (Optional) CF card is less than 1%, or CF memory card is not inserted
BYPASS SIGNAL
PIN No.: TB2-6
OUT-12
Output when in the BYPASS / PROGRAM mode.
OUTPUT BANK [OFF]
*Firmware version 1.310 or
later
Summary of Contents for Handheld Nutrunner HFC3000
Page 2: ...www fec usa com Copyright 2017 FEC AUTOMATION SYSTEMS All Rights Reserved ...
Page 14: ...Notes ...
Page 15: ...Chapter 1 Outline PAGE 1 1 Chapter 1 Outline 1 ...
Page 21: ...Chapter 2 Specifications PAGE 2 1 Chapter 2 Specifications 2 ...
Page 28: ...Chapter 2 Specifications PAGE 2 8 Blank Page ...
Page 29: ...Chapter 3 Sysytem Description PAGE 3 1 Chapter 3 System Description 3 ...
Page 36: ...Chapter 3 System Description PAGE 3 8 Memo ...
Page 37: ...Chapter 4 Installation and Wiring PAGE 4 1 Chapter 4 Installation Wiring 4 ...
Page 67: ...Chapter 5 Power Up and Operational Tests PAGE 5 1 Chapter 5 Power Up and Operational Tests 5 ...
Page 71: ...Chapter 6 Fastening Operation PAGE 6 1 Chapter 6 Fastening Operation 6 ...
Page 151: ...Chapter 7 Troubleshooting PAGE 7 1 Chapter 7 Troubleshooting 7 ...
Page 169: ...Chapter 8 Options PAGE 8 1 Chapter 8 Options 8 ...
Page 181: ...Chapter 9 Fieldbus I O Interfaces PAGE 9 1 Chapter 9 Fieldbus I O Interfaces 9 ...
Page 229: ...Chapter 9 Fieldbus I O Interfaces PAGE 9 49 Blank Page ...
Page 230: ......
Page 231: ......