Chapter 9 Fieldbus I/O Interfaces
PAGE 9-32
9-3-6 System Area PLC Handshake
Enabling the CC-Link connection to the PLC
PLC Ladder logic is required to enable the CC-Link communication link. The logic must address the enable bit
(Initial Data Processing Request) of which the address changes based on the size setting used. The last 16 bits
of both the Inputs and outputs (no matter what size is configured) is the CCLINK system setting area and this is
where the link must be enabled.
Below is an example of CC-Link configuration settings made by GX Developer software and how memory is allocated. This
configuration has 3 sets of HFC3000 controllers connected with 4 occupied stations / 8 extended cyclic cycles. (I/O 896 Points,
Message 72 Words)
Item
HFC3000
(System 1)
HFC3000
(System 2)
HFC3000
(System 3)
CC-Link Station Number
1
5
9
Configured Size (4 occupied stations/8Cyclic cycles)
896 (880 useable)
896 (880 useable)
896 (880 useable)
EM-STOP (First bit of PLC output)
Y100
Y480
Y800
Total Reject (First bit of AFC3000 Output)
X100
X480
X800
Part ID message output to AFC3000 Controllers
D4000
D4072
D4144
Fastening result message from AFC3000 controllers
D1000
D1072
D1144
CC-Link Request address
X478
X7F8
XB78
CC-Link Enable address
Y478
Y7F8
YB78
In the case of the first HFC3000 System (1) (shown in the table above), the PLC program is set so that when the
888th (378h) bit (
“Initial Data Processing Request”) in the (CC-Link Reserved) system area (X area) is turned “ON”,
the output at the 888th (378h) bit (
“Initial Data Processing Complete”) of the system area (Y area) is set “ON”.
(
Note: See pages 8 & 14 for CCLINK handshaking signal location
)
Since the X/Y starting address of (System 1) is configured to start at X100 and Y100, this must be added to the
addresses and therefore (100h+378h) 478h is specified for the X area and the Y area as shown in the PLC Logic
diagram below
to enable Station 1’s link.
For Station 2’s link, the starting address (X/Y480) is added to the 888
th
(378h) bit for that station which is address
(480h + 378h) X/Y7F8.
For Station 3’s link, the starting address (X/Y800) is added to the 888
th
(378h) bit for that station which is address
X/YB78.
PLC Logic example that would be required to enable the CC-Link in the three systems listed above
Summary of Contents for Handheld Nutrunner HFC3000
Page 2: ...www fec usa com Copyright 2017 FEC AUTOMATION SYSTEMS All Rights Reserved ...
Page 14: ...Notes ...
Page 15: ...Chapter 1 Outline PAGE 1 1 Chapter 1 Outline 1 ...
Page 21: ...Chapter 2 Specifications PAGE 2 1 Chapter 2 Specifications 2 ...
Page 28: ...Chapter 2 Specifications PAGE 2 8 Blank Page ...
Page 29: ...Chapter 3 Sysytem Description PAGE 3 1 Chapter 3 System Description 3 ...
Page 36: ...Chapter 3 System Description PAGE 3 8 Memo ...
Page 37: ...Chapter 4 Installation and Wiring PAGE 4 1 Chapter 4 Installation Wiring 4 ...
Page 67: ...Chapter 5 Power Up and Operational Tests PAGE 5 1 Chapter 5 Power Up and Operational Tests 5 ...
Page 71: ...Chapter 6 Fastening Operation PAGE 6 1 Chapter 6 Fastening Operation 6 ...
Page 151: ...Chapter 7 Troubleshooting PAGE 7 1 Chapter 7 Troubleshooting 7 ...
Page 169: ...Chapter 8 Options PAGE 8 1 Chapter 8 Options 8 ...
Page 181: ...Chapter 9 Fieldbus I O Interfaces PAGE 9 1 Chapter 9 Fieldbus I O Interfaces 9 ...
Page 229: ...Chapter 9 Fieldbus I O Interfaces PAGE 9 49 Blank Page ...
Page 230: ......
Page 231: ......