Installation
8.
INSTAL
LAT
ION
Ele
ctrica
l co
nne
ctio
ns
302
Ref.2003
· 262 ·
QC-PDS
HARDWARE
Spindle motor
For single-drives, size|1
The power connection for spindle motor to a QC-DR-
-F
, size|1 single-
drive is made using a multi-pole MPC-4xS cable via terminals U, V and W
of the X11A connector. The connection between the chassis and the
protective earth (PE) is made via any of the M5 screws of the protective
earth (PE) on the vertical plates next to the X11A connector found on the
upper part of the drive. The shield of the multi-pole MPC-4xS power cable
is connected to the protective earth at both cable ends. On the drive side
via the GP-1 protective earth bar.
Be sure to strip the power cable to expose the shield at both ends. Use a
metal clamp complete the connection to the GP-1 on the drive side. See
connection diagrams in
.
See figure.
NOTE.
No spindle motor in the FAGOR catalog comes with a brake.
F. H8/19
Power connection of the spindle motor to the single-drive, size|1.
P E
3
M
c h a s s i s
W
V
U
X 1 1 A
U
U
V
W
U
U
G P - 1
M 5
PE
42 A
QC-DR-
-F
SIZE|1
X11A
X11A
QC-DR-040-F
QC-DR-055-F
SPINDLE MOTOR
PE.
Ground bolt
FM7. TERMINAL BOX
23 A
X11A
QC-DR-030-F
multi-pole MPC-
4xS
cab
le
w
ithout
conn
ector
s
WARNING.
When running the cables for the power connection between
the QC-DR-
-F
, size|1 single-drive and the spindle motor, connect the U
terminal of the X11A connector to the terminal corresponding to the U
phase of the motor. Perform the same procedure with terminals V-V, W-W.
See X11A connector in chapter 3. The multi-polar MPC-4xS cable has
metallic shielding (shield) that, in order to be compliant with the EC
marking, must be connected to the GP-1 protective earth bar on the side of
the drive. At the motor end, to the protective ground screw in the terminal
box. Please note that a non-compliant connection could result in improper
performance.
Summary of Contents for QC-PDS
Page 1: ...DRIVE QC PDS Hardware manual Ref 2003...
Page 6: ...6 I 6 Ref 2003 6 QC PDS HARDWARE This page intentionally left blank...
Page 16: ...16 Ref 2003 16 Previous I QC PDS HARDWARE This page intentionally left blank...
Page 18: ...18 Ref 2003 18 Previous II QC PDS HARDWARE This page intentionally left blank...
Page 80: ...2 POWER SUPPLIES Power supplies 80 Ref 2003 QC PDS HARDWARE...
Page 138: ...3 DRIVES Drives 138 Ref 2003 QC PDS HARDWARE...
Page 174: ...4 AUXILIARY MODULES Auxiliary modules Ref 2003 174 QC PDS HARDWARE...
Page 302: ...8 INSTALLATION Installation Ref 2003 302 QC PDS HARDWARE...
Page 366: ...12 COMMERCIAL MODELS Commercial models Ref 2003 QC PDS HARDWARE 366...
Page 367: ...ANNEXES...
Page 368: ...ANNEX A1...
Page 383: ...ANNEX A2...
Page 398: ...ANNEX A3...
Page 418: ......
Page 419: ......