INSTRUCTION MANUAL DAAB AUTOMATIC CONTROL UNIT EP105
35
Revision 3
Safety edge
No.
Name
Range
Factory Setting Ref. page
S
C101 Safety edge acknowledgement SE.C1
0 – 1
0
0
Disabled
1
Enabled
S
C102 Output for self-test of external protection
0 – 4
0
0
Check disabled, open output.
1
Closed to GND on activation, normally open.
2
Closed to V+24 VDC on activation, normally open.
3
Open on activation, normally closed to GND.
4
Open on activation, normally closed to +24 VDC.
S
C103 Function of safety edge input during test of
external safety edge unit
1 – 2
1
1
Low resistance during test
2
High resistance during test
S
C104 Connection and safety edge function
1 – 3
1
1
SE.C1 or SE.C2 can be connected to either motor 1 or motor 2.
SE.O1 or SE.O2 can be connected to either motor 1 or motor 2.
Both safety edges reverse/stop an active motor
2
SE.C1 and SE.O1 must be connected to motor 1
SE.C2 and SE.O2 must be connected to motor 2
The safety edge function is attached to the motor concerned
3
SE.C1 or SE.C2 can be connected to either motor 1 or motor 2.
SE.O1 can be connected for protection function in opening for motor 1 and motor 2.
The safety edges reverse/stop an active motor
SE O2 stops an active motor in both opening and closing and overrides channel C142
C105
Halved speed after activated safety edge.
Only when using a frequency converter.
0 - 1
0
0
Disabled
1
Active
S
C111 Selects function for safety edge SE.C1
0-2
2
0
SE.C1 disabled
1
Limits according to set value in C115
2
Fixed limits between 5 kΩ and 15 kΩ
S
C112 Reverse/stop with activated safety edge SE.C1
(KSS)
1 - 2
1
1
Reverse
2
Stop
S
C113 Control of external protection connected to SE.C1 0 - 1
1
0
No check
1
Test of protection connected to SE.C1 if C102 is enabled
C114
Reading impedance SE.C1
00.0-99.9 kΩ
S
C115 Setting impedance value for safety edge SE.C1
Set to 1 only at C111.
1.0-9.9 kΩ
8.2