INSTRUCTION MANUAL DAAB AUTOMATIC CONTROL UNIT EP105
20
Revision 3
• Commissioning of drive unit 2
Preparations:
C999 is set to 2. Open half 1 and set L001 to 0 to keep drive unit 1 in open position Set C033 to 5, service
position.
Direction of movement:
Start L002 to 4, hold-to-run without limits. Check that the motor arm attachment is running in the
right direction by pressing the OPEN or CLOSE buttons on the automatic control unit. For change of direction of rotation,
see section on Connection in EP105 Instruction Manual.
Open and closed position:
Connect the gate half to drive unit 2 and enter the positions for open and closed After this,
L002 is set to 1, encoder.
L110=1, Motor 1 Left position
L120=2; Motor 2 Right position
L123, Closed position
L122, Open position
L121, Position readout
Motor protection:
Read the motor current during operation in C261 and enter this value in C262 for opening and in C263
for closing. E202 means that the entered value is set too low. E207 means that the entered value is set too high.
Load guard:
C999 is set to 3. In a hinged gate application personal protection is not normally required, and C240 is set
to 0.00. Set C033 to 3, pulse to activate the load guard. After the load guard has tripped, the indication M2 flashes and the
message n073 or n074 is shown on the display and in the error code list in C903. Check that the setting in the load guard
in C242 and C243 is just high enough not to cause material damage, but at the time is so high that it is guaranteed to open
depending on weather conditions and mechanical changes.
Safety edges:
Check the safety edges on gate half 2 by activating the safety edges during movement. Note that safety
edge function in opening is closed in C141. In activated safety edge during closing, the gate must reverse to the fully open
position, while in opening it must reverse to closed position during the time in C494. Flashing indication for SE.C2 or
SE.O2 means that the safety edge has been activated, but is now disabled.
Additional boards:
Set C999 to 4. Channels C702 to C712 show or hide channels for additional boards.
If e.g. DB407, Output board, to be used set C707 to 1
Finishing:
Set C999 to 0, display of all channels Set L001 to 1, encoder and make find adjustments to the gate halves in closed
position using L113 and L123. Note all channels in EP105 Instruction Manual and the Log Book.