Automatic closing
No.
Name
Range
Factory Setting Ref. page
C500
Time before automatic closing
000,0 means disabled function
000.0-600.0 seconds
000.0
C510
Time before closing, after passage, on photocell
closing and loop closing.
Subordinated to C351, d151 and d251.
00-99 seconds
00
C520
Blocking time for automatic closing after the stop
button is activated 000 means disabled function
000 and 020-600
seconds
000
C591
Closing using loops and photocell
00 - 14
00
00
Disabled
01
Presence detection, LOOP1 must first be activated, closes when LOOP1 is clear.
02
Presence detection, LOOP2 must first be activated, closes when LOOP2 is clear.
03
Presence detection, LOOP1 or LOOP2 must first be activated, closes when either LOOP1 or LOOP2
is clear.
04
Presence detection, PHOTO must first be activated, closes when PHOTO is clear.
05
Presence detection, PHOTO and LOOP1 must first be activated simultaneously, then close when
either PHOTO or LOOP1 is clear.
06
Presence detection, PHOTO and LOOP2 must first be activated simultaneously, then close when
either PHOTO or LOOP2 is clear.
07
Presence detection, PHOTO LOOP1 and LOOP2 must first be activated simultaneously, close when
either PHOTO, LOOP1 or LOOP2 is clear.
08
Presence detection, LOOP1 and LOOP2 must first be activated simultaneously, close when either
LOOP1 or LOOP2 is clear.
09
Direction sensing, LOOP1 must first be activated, during the time LOOP2 must be activated, then
LOOP1 must be clear, closes when LOOP2 is clear.
10
Direction sensing, LOOP1 must first be activated, during the time PHOTO must be activated, then
LOOP1 must be clear, closes when PHOTO is clear.
11
Direction sensing, LOOP2 must first be activated, during the time LOOP1 must be activated, then
LOOP2 must be clear, closes when LOOP1 is clear.
12
Direction sensing, LOOP2 must first be activated, during the time PHOTO must be activated, then
LOOP2 must be clear, closes when PHOTO is clear..
13
Direction sensing, PHOTO must first be activated, during the time LOOP1 must be activated, then
PHOTO must be disabled,closes when LOOP1 is clear.
14
Direction sensing, PHOTO must first be activated, during the time LOOP2 must be activated, then
PHOTO must be disabled, closes when LOOP2 is clear.