INSTRUCTION MANUAL DAAB AUTOMATIC CONTROL UNIT EP105
49
Revision 3
Programmable input 4
No.
Name
Range
Factory Setting Ref. page
P400
Programmable input 4
0 - 1
1
0
Disabled
1
Enabled
P460
Control function
0 - 5
2
0
Disabled
1
Open
2
Close
3
Stop
4
Open/close
5
Open/stop/close
S
P461 Type of control signal when activated
1 - 2
2
1
Pulse
2
Signal for as long as the input is activated
P462
Half operation
1 - 3
3
1
Motor 1
2
Motor 2
3
Motors 1 and 2
P463
Limited opening
0 - 1
0
0
Disabled
1
Opening according to set time in channel L216/L226 or number of degrees in L116/L126 if encoder
is used.
P470
Motor lock
0 - 1
0
0
Disabled
1
The barrier cannot be operated without a signal at programmable input 4.
If the signal disappears ongoing movement stops.
P475
Opening via input after activation during set
time, input will not open the gate until it has been
activated for the set time.
0.0-9.9 seconds
0.0
P480
Park
0 - 2
0
0
Disabled
1
Automatic closing disabled after the input is activated, reset by another control signal
2
Automatic closing disabled by a constant signal.
P490
Interlock opening
0 - 1
0
0
Disabled
1
Opens the local door if P460 is set to open, and passes the signal on to the remote door
P496
Blocking disabled for local and remote doors. Works
only with a constant signal.
0 - 1
0
0
Disabled, function according to channel C614
1
Blocking disabled
P498
Automatic closing switched off for remote door.
Only works if there is a constant signal
0 - 1
0
0
Disabled, function according to channel C500
1
Automatic closing switched off