INSTRUCTION MANUAL DAAB AUTOMATIC CONTROL UNIT EP105
48
Revision 3
Programmable input 3
No.
Name
Range
Factory Setting Ref. page
P300
Programmable input 3
0 - 1
1
0
Disabled
1
Enabled
P360
Control function
0 - 5
1
0
Disabled
1
Open
2
Close
3
Stop
4
Open/close
5
Open/stop/close
S
P361 Type of control signal when activated
1 - 2
2
1
Pulse (hold-to-run mode not possible)
2
Signal for as long as the input is activated
P362
Half operation
1 - 3
3
1
Motor 1
2
Motor 2
3
Motors 1 and 2
P363
Limited opening
0 - 1
0
0
Disabled
1
Opening according to set time in channel L216/L226 or number of degrees in L116/L126 if encoder
is used.
P370
Motor lock
0 - 1
0
0
Disabled
1
The barrier cannot be operated without a signal at programmable input 3.
If the signal disappears ongoing movement stops.
P375
Opening via input after activation during set
time, input will not open the gate until it has been
activated for the set time.
0.0-9.9 seconds
0.0
P380
Park
0 - 2
0
0
Disabled
1
Automatic closing disabled after the input is activated, reset by another control signal
2
Automatic closing disabled by a constant signal.
P390
Interlock opening
0 - 1
0
0
Disabled
1
Opens the local door if P360 is set to open, and passes the signal on to the remote door
P396
Blocking disabled for local and remote doors. Works
only with a constant signal.
0 - 1
0
0
Disabled, function according to channel C614
1
Blocking disabled
P398
Automatic closing switched off for remote door.
Only works if there is a constant signal
0 - 1
0
0
Disabled, function according to channel C500
1
Automatic closing switched off