INSTRUCTION MANUAL DAAB AUTOMATIC CONTROL UNIT EP105
45
Revision 3
Limit switch
No.
Name
Range
Factory Setting Ref. page
L203
A
Setting limited running time (Not used with
encoder)
001-999 seconds
001
L211
A
Running time readout, motor 1
000-999 seconds
L212
AB
Run-on time following limit switch open, motor 1
0.00-7.99 seconds
0.00
L213
A
Run-on time following limit switch closed, motor 1
0.00-7.99 seconds
0.00
L216
A
Set limited opening, motor 1 with limit switch
00.3-99.9 seconds
05.0
L221
A
Running time readout, motor 2
000-999 seconds
L222
AC
Run-on time following limit switch open, motor 2
0.00-7.99 seconds
0.00
L223
A
Run-on time following limit switch closed, motor 2
0.00-7.99 seconds
0.00
L226
A
Set limited opening, motor 2 with limit switch
00.3-99.9 seconds
05.0
Time control
L311
Time readout for motor 1
00.1-99.9 seconds
L312
A
Set time for motor 1
00.1-99.9 seconds
00.1
L321
Time readout for motor 2
00.1-99.9 seconds
L322
A
Set time for motor 2
00.1-99.9 seconds
00.1
A = Only displayed if L001 and/or L002 are set to 2 or 3.
B = Only displayed if L001 = 1 and C202 = 4, frequency converter.
C = Only displayed if L002 = 1 and C202 = 4, frequency converter.