b11: reserved
b12: parameters conversion failed
AlgS
1795
RO
- - - -
- - - -
- - - -
- - - -
User
SH algorithm status
b0:
measure not acquired
b1:
algorithm halted
b2:
bypass algorithm (manual)
b3:
LoSH algorithm is running
b4:
LoSH alarm
b5:
HiSH algorithm is running
b6:
HiSH alarm
b7:
LOP algorithm is running
b8:
LOP alarm
b9:
MOP algorithm is running
b10: MOP alarm
b11: LP
b12: LP alarm
CoWA 1796
RO
0
21
- - - -
- - - -
User
configuration warnin
0 = correct configuration
1 = incorrect config. for start-up
2 = invalid value for parameter Pia1
3 = invalid value for parameter Pia2
4 = invalid value for parameter Pia3
5 = invalid value for parameter Pia4
6 = Piu1 configuration matches other
Piux
7 = Piu2 configuration matches other
Piux
8 = Piu3 configuration matches other
Piux
9 = incorrect configuration Piu4
10 = mismatch between Pia1 and Piu1
11 = mismatch between Pia2 and Piu2
12 = mismatch between Pia3 and Piu3
13 = mismatch between Pia4 and Piu4
14 = awaiting configuration AI1
15 = awaiting configuration AI2
16 = awaiting configuration AI3
17 = awaiting configuration AI4
18 = awaiting analog configurations
19 = error writing Xmax probe 4
scaling
20 = error writing Xmax probe 4
scaling
21 = no
primary
temperature
or
pressure probe configured
22 = copy valve parameters error
23 = valve selection error