9.9
Parameters error
Bit 12 of Alarm status (AlSt) indicates that there was a problem during the automatic conversion of the parameters of
temperature and/or pressure and it is possible that not all parameters have been successfully converted.
The automatic conversion of the parameters is performed only at the reset after a change in parameters Ph60 and/or
Ph61.
If this alarm occurs, the user should check and correct all the parameters of temperature and pressure, cancel the
alarm leading to 1 bit 0 of the variable Command (Cmd), and then reset the EVDRIVE04.