EVCO S.p.A.
EVDRIVE04 | User manual ver. 1.1 | Code 144EPD4I114
Page 41 of 78
7.9
List of configuration parameters
The following is a complete list of parameters managed by the application, each with a short code, the ModBus address
(Adr), brief description, default values and limits, measurement units (U), the menu in which they are accessed (M)
and the notes.
The menus are split into levels: U (User), I (Installer, protected by first-level password), M (Manufacturer, protected
by the second level password.
All the parameters in the User menu are freely modifiable and their modification is immediately applied. The Installer
parameters are usually loaded by the application only when the machine is in the
Stand-by off
(10), and can be
changed only in this state.
The variable
Parameters status
(ParS) indicates that the modified parameters have been acquired but are not currently
in use. To finalize the acquisition, it is necessary to reset or disable the valve. If the variable is set to 0, it means that
the new parameters are already active.
The correct procedure for changing Installer and Manufacturer parameters is:
•
disable the valve
•
modify the parameters
•
verify the
Parameters status
(ParS) value
•
reset the board if requested by
Parameters status
(ParS)
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Common parameters
Pr01
1537
RW
0
8
-
6
Installer
Main control type
0: none
1: analog positioner on AI1
(0÷20 mA)
2: analog positioner on AI2 (0÷5V
ratiometric)
3: analog positioner on AI3
(4÷20 mA)
4: analog positioner on AI4 (0÷10V)
5: analog positioner on AI4
6: Superheat control
7: analog positioner on AI3 (4÷20 mA)
and AI4 (0÷10V)
8: hot gas bypass
Pr04
1537
RW
1
2
-
1
User
SH parameters set selection
1: parameters Set 1
2: parameters Set 2
Pr05
1598
RW
0.00
100.00
%
0.00
Installer
Probe alarm position
If Pr05 = 0% the valve is closed to 0
steps instead Minimum regulation
step
Pr06
1599
RW
0
9
-
0
Installer
Enabling mode
0 = from digital input DI1
or DI2 (stand-alone)
1 = from digital input DIHV (stand-
alone)