EVCO S.p.A.
EVDRIVE04 | User manual ver. 1.1 | Code 144EPD4I114
Page 44 of 78
Pa02
1571
RW
5
120
s
30
Installer
communication alarm delay
Pa10
1572
RW
0
1
- - - -
0
Installer
enable LoSH alarm
1 = yes
Pa11
1573
RW
0.0
25.0
K
0.5
Installer
LoSH alarm hysteresis
Pa12
1574
RW
0
250
min
3
Installer
LoSH alarm delay
Pa20
1575
RW
0
1
- - - -
0
Installer
enable HiSH alarm
1 = yes
Pa21
1576
RW
0.0
25.0
K
1.0
Installer
HiSH alarm hysteresis
Pa22
1577
RW
0
250
min
3
Installer
HiSH alarm delay
Pa30
1578
RW
0
1
- - - -
0
Installer
enable low pressure alarm
1 = yes
Pa31
1579
RW
0.00
45.00
barG
0.00
Installer
low pressure setpoint alarm
Pa32
1580
RW
0.20
1.00
barG
0.30
Installer
low pressure alarm hysteresis
Pa33
1581
RW
0
250
min
3
Installer
low pressure alarm delay
Pa34
1588
RW
0
250
s
180
Installer
low pressure alarm bypass
Pa40
1582
RW
0
1
- - - -
0
Installer
enable LOP alarm
1 = yes
Pa41
1583
RW
0.0
10.0
K
1.0
Installer
LOP alarm hysteresis
Pa42
1584
RW
0
250
min
3
Installer
LOP alarm delay
Pa50
1585
RW
0
1
- - - -
0
Installer
enable MOP alarm
1 = yes
Pa51
1586
RW
0.0
10.0
K
1.0
Installer
MOP alarm hysteresis
Pa52
1587
RW
0
250
min
3
Installer
MOP alarm delay
Pa53
1633
RW
0.0
25.0
K
7.0
Installer
MOP maximum dSH applicable
Pa54
1634
RW
0.0
25.0
K
8.0
Installer
MOP band
Pa55
1635
RW
0
255
10 s
15
Installer
MOP filter time constant
Pa56
1636
RW
0
255
min
10
Installer
MOP bypass delay
Pa57
1696
RW
0
100
%
0
Installer
MOP forced delta
Pa58
1697
RW
0
255
s
0
Installer
MOP forced time
Pa70
1590
RW
0
1
- - - -
0
Installer
enable main power supply alarm
1 = yes
Pa71
1591
RW
0
60
s
1
Installer
main power supply alarm delay
Pa75
1592
RW
0
1
- - - -
0
Installer
enable backup battery alarm
1 = yes
Pa76
1593
RW
0
60
s
35
Installer
backup battery alarm delay