EVCO S.p.A.
EVDRIVE04 | User manual ver. 1.1 | Code 144EPD4I114
Page 43 of 78
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Valve and driver: debug
Prd0
1616
RW
25
1000
step/s
25
User
debug step rate
Prd1
1617
RW
0.00
Prd2
%
0.00
User
debug minimum position
Prd2
1618
RW
Prd1
100.00
%
100.00
User
debug maximum position
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Valve and driver: backup battery
Pb01
1619
RW
0
1
- - - -
0
Installer
backup battery
1 = present
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Parameters set n. 1
Pc01
1539
RW
3.0
25.0
K
6.0
User
SH setpoint
Pc02
1540
RW
1.0
3.0
K
2.0
User
LoSH setpoint
Pc03
1541
RW
10.0
40.0
K
15.0
User
HiSH setpoint
Pc04
1542
RW -200.0
40.0
°C
40.0
User
Set1 LOP temperature
Pc05
1543
RW
-40.0
40.0
°C
40.0
User
MOP temperature
Pc06
1544
RW
-30.0
40.0
°C
10.0
User
Set1 Bypass temperature set-point
Pc13
1681
RW
1.0
100.0
K
40.0
User
PID proportional band
Pc14
1682
RW
0
999
s
120
User
PID integral time
Pc15
1687
RW
0
999
s
30
User
PID derivative time
Pc20
1690
RW
1
255
s
5
Installer
start-up delay
Pc21
1693
RW
0.00
100.00
%
50.00
Installer
start-uo position
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Parameters set n. 2
Pp01
1547
RW
3.0
25.0
K
6.0
User
SH setpoint
Pp02
1548
RW
1.0
3.0
K
2.0
User
LoSH setpoint
Pp03
1549
RW
10.0
40.0
K
15.0
User
HiSH setpoint
Pp04
1550
RW -200.0
40.0
°C
-40.0
User
Set2 LOP temperature
Pp05
1551
RW
-40.0
40.0
°C
40.0
User
MOP temperature
Pp06
1552
RW
-30.0
40.0
°C
10.0
User
Set2 Bypass temperature set-point
Pp13
1685
RW
1.0
100.0
K
40.0
User
PID proportional band
Pp14
1686
RW
0
999
s
120
User
PID integral time
Pp15
1689
RW
0
999
s
30
User
PID derivative time
Pp20
1692
RW
1
255
s
5
Installer
start-up delay
Pp21
1695
RW
0.00
100.00
%
50.00
Installer
start-uo position
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Protections and alarms
Pa01
1570
RW
0
1
- - - -
0
Installer
enable communication alarm
1 = yes