EVCO S.p.A.
EVDRIVE04 | User manual ver. 4.1 | Code 144EPDE114
page 62 of 78
4
Invalid value for parameter PIA3
5
Invalid value for parameter PIA4
6
PIu1 configured as another Piux
Parameters Piu1, Piu2, Piu3 and Piu4 must
each
7
PIu2 configured as another PIux
have different values, or null.
8
PIu3 configured as another PIux
Checked only if Pr01 ≥ 6
9
PIu4 configured as another Piux
10
Contradiction between analog input type
Check parameters Piax and Piux.
(Pia1) and its utilization (Piu1)
11
Contradiction between analog input type
Temperature is measured using probes of
(Pia2) and its utilization (Piu2)
type NTC, pt1000, or scaling; pressure
12
Contradiction between analog input type
is measured using current, tension or scaling
(Pia3) and its utilization (Piu3)
probes.
13
Contradiction between analog input type
Checked only if Pr01 ≥ 6
(Pia4) and its utilization (Piu4)
14
Awaiting AI1 configuration
Wait
15
Awaiting AI2 configuration
Wait
16
Awaiting AI3 configuration
Wait
17
Awaiting AI4 configuration
Wait
18
Awaiting analog inputs configurations
Wait
19
Limit error Xmax probe scaling
20
Limit error Xmax probe scaling
21
No AI configured for primary temperature
Check PIu1, PIu2, PIu3 and PIu4 parameters
or pressure probe input and ensure one is
dedicated to the primary temperature probe,
and another to the primary pressure probe.
Checked only if Pr01 ≥ 6
22
Error when copying the selected valve parameters Try copyng again
to the generic valve
23
A valve with incorrect parameters was selected
Set the valve parameters correctly and
restart the instrument
24
A probe is not properly configured
Check PIAx prameters
9.4
Communication error
A communication error is signalled only if a suitable communication mode is selected (Pr06 ≥ 2), and the
communication alarm is active (Pa01 = 1). Under these conditions, the driver expects the controller to periodically
refresh the Enable valve command (EnaV).
If the refresh does not happen for more than half the time set in Communication alarm delay (Pa02), a warning is
given. If the refresh does not happen for more than the time set in Communication alarm delay (Pa02), the
communication is considered lost and communication alarm is set.
Management of this alarm depends on the mode selected. If Pr06 = 2÷5, a communication alarm state will cause the
valve to be forced to the position determined by Communication error position (Pr48), and will then enter the
Communication alarm (5) until the positioning process has completed and the communication start again. If Pr06 =
6÷9, a communication alarm status will place the valve into standalone mode, and DI1 enable the valve.
When the communication alarm is cleared, the valve will automatically return to the online mode.