EVCO S.p.A.
EVDRIVE04 | User manual ver. 1.1 | Code 144EPD4I114
Page 48 of 78
probe
2 = suction pressure backup probe
Pia1
1647
RW
1
30
- - - -
1
Installer
analog input AI1 probe type (used if
Piu1 = 1 or 2)
1 = NTC probe
6 = Pt 1000 probe
10 = 4÷20 mA transducer
(0÷10 Barg)
11 = 4÷20 mA transducer
(0÷16 Barg)
12 = 4÷20 mA transducer
(0÷30 Barg)
13 = 4÷20 mA transducer
(0÷50 Barg)
30 = scaling
AI1T
517
RW
2
7
- - - -
???
User
AI1 type (used if Piu1 = 0)
2 = NTC
3 = 0-20 mA
4 = 4-20 mA
5 = reserved
6 = reserved
7 = Pt 1000
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Probe settings: analog input AI1
scaling
P1Xty 1648
RW
0
1
- - - -
0
Manufact.
X type
0 = 0-20 mA
1 = 4-20 mA
P1XM
1649
RW
P1Xm
0:20.00
1:20.00
2:5.00
- - - -
20.00
Manufact.
X max value
P1Xm 1650
RW
0:0.00
1:4.00
2:0.00
P1XM
- - - -
0.00
Manufact.
X min value
P1Tty 1651
RW
0
1
- - - -
0
Manufact.
Y type
0 = barG
1 = barA
P1YM
1652
RW
P1Ym
300.00 barG/barA
1.00
Manufact.
Y max value
P1Ym 1653
RW
-
300.00
P1YM
barG/barA
0.00
Manufact.
Y min value
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Probe settings: analog input AI2
Piu2
1654
RW
0
2
- - - -
0
Manufact.
analog input AI2 function