ERRSUM
value
Output error counter in total since operation,
max. 65000
ERROWD
1-30
value
Output of the requested OWD number
Error counter max. 65000
Default: 255
Note: error counters are reset at midnight.
ERRLISTALL
List output of all stored OWDs
Error counter per OWD, max. 65000
Default: 255
Note: error counters are reset midnight.
ERRLISTALL1
List output of all 30 OWDs
Error counter max. 65000
Default: 255
Note: error counters are reset at midnight.
22.5.3. One Wire Device Command (OWD)
Queries affecting the entire 1-Wire network
GET
OWD NAME
OWD-
number
Output of the stored name to a
1-Wire device (OWD)
FORMAT
value
Output of decimal places for temperature sensors.
Range: 0-2 digits
Default: 2 digits, format as integer value, last two
digits are output as decimal values.
STATUS
OWD-
number
Output of the status of a 1-Wire device (OWD)
0= no read errors
1-3= number of current read errors
5= device not readable. There is no
data output for this 1-Wire block
10= OWD space is not occupied
TYPE
OWD-
number
Output of the 1-Wire device (OWD) type,
e.g. DS1820 for a temperature sensor or
11220 as assigned article number
DS2408INV
value
Data output for the 8-fold I/O blocks DS2408
inverted?
0=no
1=yes
DS2450ADC
value
Setting of the data output for output of DS2450
blocks
0=16Bit Integer Values
1=Analog voltage in mV with two decimal places,
e.g. 2.56V corresponds to 2560
GRPGET
OWD-
number
Output of group addresses for an OWD number or
for all OWDs in list format.
GRPLIST1
Output of the group addresses for all OWDs in list
format.
22.5.4. Get KEY Command
Commands which affect the 1-Wire devices in detail
1
2
3
4
5
Description
GET
KEY
DATA
Status query of data output for iButton with
command "DATA".
Value:
0 = if iButton available; data output with serial
number
1 = if iButton is available; data output with "1
2 = Data output if iButton is available "1", if not
available "0"