Programming Manual Controller-Gateway-Station V1.0 R1.1
Page 67 of 77
22.3.
Set One Wire Bus Command
Commands valid for the entire 1-Wire network
1
2
3
4
5
Description
SET
OWB
RST
One Wire Bus Reset
OWDID
0 or 1
Switches the output of the module name either
with "OWD" or the own serial number
0=Output "OWD",
1=Output of device serial number
Default = 0
OWDIDFORMAT
0 or 1
Switches the output of the OWD serial number
with family code beginning left or right.
0=Output family code left
1=Edition family code right
Default = 0
SEARCHALL
Starts a manual search of all 1-Wire devices,
the previous OWD list will be overwritten.
Note
: The search function is only
recommended for a new system, as the OWD
list is overwritten and unconnected devices are
deleted.
SEARCH
0-2
Sets the One Wire Mode
0=no search
1=Cyclic complete search (sequence of
devices can change)
2=Adaptive cyclical search for new devices
New devices are written to the first free space
in the OND list.
Default: 2
SEARCHTIME
10-240
Setting the cycle time for the search function
Default: 10 seconds
SAVE
Saves the OWD list in the S-RAM,
After restart the 1-Wire Controller / 1-Wire
Gateway the list can be loaded.
This command also permanently saves the
OWD names.
LOAD
Loads the saved OWD list with the last saved
1-Wire devices
POLLTIME
1-240
Cycle time for querying of all 1-Wire modules
of the bus.
Note: The time can only be selected greater
than the transmission time (datatime) of the
data. Exception, if datatime = 0
Default: 2 seconds
MOVE
1-30
1-30
Moves a One Wire device (OWD) within the
block list.
One Wire device
FROM
OWD list location
TO
OWD list location
DELNO
1-30
Deletes a One Wire device from the OWD list,
but not from the list stored in the S-RAM.
DELALL
Deletes all 1-Wire devices from the OWD list,
but not from the permanently stored OWD list
(S-RAM list).
DISALL
All 1-Wire devices are deactivated but not
deleting them.
DELMEM
Deletes all permanently stored 1-Wire devices
(OWDs) in the 1-Wire Controller / 1-Wire
Gateway (EEPROM). This command also
deletes the stored OWD names