42
Installation Instructions - EmoTouch 3
Electrical installation
EN
Sauna heater
The neutral conductor (N) of the sauna heater must always be connected
because, in humidity mode, one phase is rerouted from the sauna heater to
the vaporiser. This results in an asymmetrical heating load and power flows
through the neutral conductor.
The switching output of the control unit for the sauna heater has a max. of
9 kW resistive load. It can be expanded as needed by an optional circuit
breaker (LSG) so that it is possible to connect sauna heaters with an output
greater than 9 kW.
To connect the optional LSG, see the installation instructions for the rele-
vant LSG.
5.3 Setting the jumper for maximum heating time
The sauna heater's heating time is limited during installation by the jumper
plug. The actual runtime can be adjusted on the control panel when mak-
ing this jumper setting.
The jumpers are included with the device and are connected by blind plug-
in.
STB
fan
light
FL FN LL LN
L1 L2 L3 N W V U N
N
WB
WM
3 4
S1 S1 N
M A I N S
O V E N
V A P.
Runtime of max. 6 h for private use
Runtime of max. 12 h for commercial use without monitoring
Runtime of max. 18 h for commercial use without monitoring
Runtime of 24 h for 7 days
For this setting, the heating time must be switched off manu-
ally.
The setting is permitted only if the sauna is used commercially
and monitored.