0170022-J0 Rev A
Page 30
7.1.4
Switching the Alpha FXM HP from Inverter mode to Line mode
The Alpha FXM HP remains in the Inverter mode for as long as the AC input circuit breaker is switched
off, or until there is loss of AC power. Backup power is provided to the load until the batteries are drained
to a preset level which triggers the Alpha FXM HP to shutdown automatically. If it is not necessary to
operate the Alpha FXM HP in the Inverter mode, switch the Alpha FXM HP back to the Line mode as
soon as possible.
To switch the Alpha FXM HP from Inverter mode to Line mode:
1. Switch
ON
the AC input circuit breaker. The Alpha FXM qualifies the line power. The LCD
displays
RETRAN
, then shows
LINE, BUCK 1, BUCK 2, BOOST 1, BOOST 2
.
If the Alpha FXM constantly switches between Inverter and Line modes because of a noisy line, broaden
the input parameter tolerances from
Normal
to
Generator
. See
AC Input > AC Input Sense > Gener
-
ator
.
Summary of Contents for Alpha FXM HP 1100
Page 1: ...Alpha FXM HP 650 1100 2000 UPS Technical Guide 0170022 J0 Effective 11 2019...
Page 2: ......
Page 4: ......
Page 12: ...viii...
Page 28: ...0170022 J0 Rev A Page 16...
Page 30: ...0170022 J0 Rev A Page 18...
Page 142: ...0170022 J0 Rev A Page 130 Figure 70 Upgrade Succeeded...
Page 144: ...0170022 J0 Rev A Page 132...
Page 146: ...0170022 J0 Rev A Page 134...
Page 148: ......
Page 149: ......