0170022-J0 Rev A
Page 89
Controller Minor, Major or Critical Alarm
To configure the relay activated by
Controller Minor Alarm,
Major Alarm,
or
Critical Alarm Status
on the LCD:
1. Go to the
System Shortcuts
menu and select
Relays
.
2. On the
Relays
page, select
Configuration
.
3. Click the edit icon of
Controller Minor Alarm
and select a relay to be energized when the
Controller Minor Alarm
status is active.
4. Click on
Controller Major Alarm
or
Controller Critical Alarm
to select a relay to be energized
for the corresponding status.
To configure the relay activated by
Controller Minor Alarm, Major Alarm,
or
Critical Alarm Status
on the web:
1. Go to
Controller > Configure Controller > Alarm and Alarm Summary Relays
page.
2. Click on the
Controller Critical Relay
edit icon to select a relay.
3. Click on
Controller Major Relay
or
Controller Minor Relay
to select a relay to be energized for
the corresponding status.
Low Battery Shutdown
To configure the relay activated by
Low Battery Shutdown Status
on the LCD:
1. Go to the
System Shortcuts
menu and select
Relays
.
2. On the
Relays
page, select
Configuration
.
3. Click the edit icon of
Low Battery Shutdown
and select a relay to be energized when the
Low
Battery Shutdown
status is active.
To configure the relay activated by
Low Battery Shutdown Status
on the web:
1. Go to
System > FXM System > Configuration > Alarms
page.
2. Click on the
Low Battery Voltage Shutdown
detail icon.
3. Click on
Low Battery Voltage Shutdown Relay
edit icon to select a relay.
9.3.17
Configure Power Outage Alarm
Frequent short power outages can generate a lot of unnecessary alarms and email notifications.
The
Power Outage Alarm
function can be configured to ignore short power outage and trigger only
when the outage is longer than a user defined duration. Similarly,
On Battery
alarm is triggered only
when the power outage is longer than the minimum power outage duration.
Summary of Contents for Alpha FXM HP 1100
Page 1: ...Alpha FXM HP 650 1100 2000 UPS Technical Guide 0170022 J0 Effective 11 2019...
Page 2: ......
Page 4: ......
Page 12: ...viii...
Page 28: ...0170022 J0 Rev A Page 16...
Page 30: ...0170022 J0 Rev A Page 18...
Page 142: ...0170022 J0 Rev A Page 130 Figure 70 Upgrade Succeeded...
Page 144: ...0170022 J0 Rev A Page 132...
Page 146: ...0170022 J0 Rev A Page 134...
Page 148: ......
Page 149: ......