0170022-J0 Rev A
Page 74
Temperature Compensation in Float
Enabled
Temperature Compensation in Absorption
Enabled
Temperature Compensation Lower Voltage Breakpoint
52.5V (48V) / 26.25V (24V)
Temperature Compensation Upper Voltage Breakpoint
55.5V (48V) / 27.75 (24V)
Battery Test
Enabled
Battery Test Trigger Input
User Input S1
Battery Test Termination Voltage
49V (48V) / 24.5V (24V)
Battery Test Timeout
1 Hour
Battery Estimation
Enabled
Battery Estimation Load Model
Resistive
AC Output Shutdown Trigger Input
User Input S3
AC Output Shutdown Operation
Manual
AC Output Shutdown Auto On Delay
30 seconds
AC Output Relay
Unassigned
AC Output Upper Disconnect Voltage
135V (120V) / 239V (230V)
AC Output Upper Reconnect Voltage
130V (120V) / 254V (230V)
AC Output Lower Reconnect Voltage
105V (120V) / 197V (230V)
AC Output Lower Disconnect Voltage
100V (120V) / 192V (230V)
Inverter Maximum Time On Enable
Disabled
Inverter Maximum Time On
5 minutes
Inverter Shutdown Voltage
42V (48V) / 21V (24V)
Inverter Manual Start up Voltage
50V (48V) / 25V (24V)
External Fan Relay
Unassigned
External Fan Temperature Sensor
Unassigned
Table 16:
FXM HP - Default Values (Continued) (Sheet 2 of 4)
Parameters
Default Settings
Summary of Contents for Alpha FXM HP 1100
Page 1: ...Alpha FXM HP 650 1100 2000 UPS Technical Guide 0170022 J0 Effective 11 2019...
Page 2: ......
Page 4: ......
Page 12: ...viii...
Page 28: ...0170022 J0 Rev A Page 16...
Page 30: ...0170022 J0 Rev A Page 18...
Page 142: ...0170022 J0 Rev A Page 130 Figure 70 Upgrade Succeeded...
Page 144: ...0170022 J0 Rev A Page 132...
Page 146: ...0170022 J0 Rev A Page 134...
Page 148: ......
Page 149: ......