0170022-J0 Rev A
Page 9
Table 3:
AVR Transition: FXM HP 650, 1100 - 120V
AVR Transition
FXM HP 650-24
120V (Vac)
FXM HP 650-48
120V (Vac)
FXM HP 1100 120V
(Vac)
Inverter to Boost 2
89.1
89
89.4
Boost 2 to Boost 1
99.5
99.5
99.9
Boost 1 to Line
113.2
113.2
113.6
Line to Buck 1
129.6
129.6
129.6
Buck 1 to Buck 2
149.3
149
148.4
Buck 2 to Inverter
170.8
170.7
170.9
Inverter to Buck 2
162.9
162.8
163
Buck 2 to Buck 1
145.5
145.4
145.6
Buck 1 to Line
127.1
126.9
126.4
Line to Boost 1
110.4
110.4
110.4
Boost 1 to Boost 2
96.1
96
96.4
Boost 2 to Inverter
84.5
84.4
84.8
Table 4:
AVR Transition: FXM HP 650, 1100, 2000 - 230V (Sheet 1 of 2)
AVR Transition
FXM HP 650-24
230V (Vac)
FXM HP 1100-48
230V (Vac)
FXM HP 2000-48
230V (Vac)
Inverter to Boost 2
161.9
162
161.4
Boost 2 to Boost 1
183
182.7
182.4
Boost 1 to Line
212.1
211.8
211.8
Line to Buck 1
248.4
248.4
248.4
Buck 1 to Buck 2
280.8
280.6
280.1
Buck 2 to Inverter
321.7
322
322.4
Inverter to Buck 2
306.8
307.1
307.5
Summary of Contents for Alpha FXM HP 1100
Page 1: ...Alpha FXM HP 650 1100 2000 UPS Technical Guide 0170022 J0 Effective 11 2019...
Page 2: ......
Page 4: ......
Page 12: ...viii...
Page 28: ...0170022 J0 Rev A Page 16...
Page 30: ...0170022 J0 Rev A Page 18...
Page 142: ...0170022 J0 Rev A Page 130 Figure 70 Upgrade Succeeded...
Page 144: ...0170022 J0 Rev A Page 132...
Page 146: ...0170022 J0 Rev A Page 134...
Page 148: ......
Page 149: ......