Optically isolated user inputs C7 and contacts C8 are used to attach an external switch panel for remote
control, or to allow the unit to control optional Alpha Off-Line Automatic Transfer Switch (ATS).
C6
The factory default layout for the C6 contact is a relay that is energized
when the unit is in Line or Inverter modes and is de-energized when in
Standby mode. It provides 48Vdc (500 mA) or 24Vdc (500mA) from the
external batteries to an external fan or other equipment.
C6 can alternatively be factory-configured as a dry contact
.
Figure 4:
Contact Layout (De-energized Shown, Factory Default for
C6)
Table 7:
C7 to C8 Optically Isolated User Inputs (Sheet 1 of 2)
Feature
Description
User Input (C7)
This relay has three contacts that are used to control the unit:
19 (S1):
Shorting this contact starts the Alpha FXM HP self test.
20 (S2):
Shorting this contact activates an alarm.
21 (S3):
Shorting this contact disables the AC output. There is no AC
output power, but the unit is still energized if connected to a battery.
A manual restart is required to put the unit back to normal operation.
22 (C):
Isolated return for contacts S1, S2 and S3.
Figure 5:
User Input Layout
Table 6:
C1 to C5 Dry Contacts (Continued) (Sheet 2 of 2)
Feature
Description
+48Vdc, 500mA
(FXM 1100/2000, 650-
48) or +24Vdc (FXM
650-24) from the
external batteries.
Microprocessor
18
16
17
Contact
C6
NC
NO
C
19
S1:Self Test
20
S2:Alarm
21
S3:Shutdown
22
Common
Summary of Contents for Alpha FXM HP 1100
Page 1: ...Alpha FXM HP 650 1100 2000 UPS Technical Guide 0170022 J0 Effective 11 2019...
Page 2: ......
Page 4: ......
Page 12: ...viii...
Page 28: ...0170022 J0 Rev A Page 16...
Page 30: ...0170022 J0 Rev A Page 18...
Page 142: ...0170022 J0 Rev A Page 130 Figure 70 Upgrade Succeeded...
Page 144: ...0170022 J0 Rev A Page 132...
Page 146: ...0170022 J0 Rev A Page 134...
Page 148: ......
Page 149: ......