Solimotion FTR20
Electrical connection
24
Hauser
6�3�5�2 Relay
The following characteristic data apply for the relay signal output (floating switchover
contact):
• Switching capacity: 250 V / 4 A, 125 V / 0.4 A or 30 V / 4 A
• Switching frequency: max. 2 Hz
Electrical connection
Relay
Connection terminals
Terminal 3 (NO)
Terminal 4 (CC)
Terminal 5 (NC)
M12 connector (Binder series 713/763)
Connector 2
Terminal 2 (NO)
Terminal 3 (CC)
Terminal 4 (NC)
Harting connector type HAN8D
Connector 2
Terminal 3 (NO)
Terminal 4 (CC)
Terminal 5 (NC)
• The contact material is also suitable for switching small-signal circuits. However, this is
possible only if no inductive loads or higher currents have been switched previously.
• For a high switching frequency, please use the solid-state relay.
• When using the Harting connector type HAN8D the maximum switching voltage is 120 V
or 50 V.
6�3�5�2 Solid-state relay
The following characteristic data apply for the solid-state relay signal output (switching
contact of a semiconductor relay):
•
Switching capacity: 30 V / 0.4 A or 40 V / 0.4 A
• Switching frequency: max. 2 Hz
Electrical connection
Solid-state relay
Connection terminals
Terminal 3 − 4
M12 connector (Binder series 713/763)
Connector 2, contact 3 − 4
Harting connector type HAN8D
Connector 2, contact 3 − 4
The polarity of the solid-state relay can be set as required.
6�3�5�3 Current output
The following characteristic data apply for the current output:
• 4-20 mA, active
• Max. load: 600 Ω
Electrical connection
Current output
Connection terminals
Terminal 3 (+) − 4 (−)
M12 connector (Binder series 713/763)
Connector 2, contact 3 (+) − 4 (−)
Harting connector type HAN8D
Connector 2, contact 3 (+) − 4 (−)