Solimotion FTR20
Electrical connection
Hauser
17
6
Electrical connection
6�1
Connection requirements
Please note the following points before connecting up the device:
• The voltage supply must match the voltage specified on the nameplate.
• Switch off the supply voltage before connecting the device.
• Connect a potential matching line to the terminal to be used on the FTR20 before
connecting the device to the power supply.
• When connecting to the public power supply, a power switch for the device must be installed
within easy reach of the device. The switch is to be identified as a disconnecting device for
the device (EN/IEC 61010).
• The cable glands and connectors are permitted for connecting fixed cables and lines only.
The operator must ensure adequate strain relief.
• The device is to be attached so that the cable gland is protected from mechanical damage
(degree of mechanical hazard "low" – impact energy: 4 joules).
• Unused guide openings must be sealed off using sealing plugs, the plastic transport sealing
plug does not meet this requirement and must therefore be replaced during installation.
For devices intended for use in hazardous areas, please read the information and comply
with the instructions in the Ex documentation (XA).
6�1�1
Required tools
Connection
Tool
Terminals and screwed contact of the optional M12 plug connector, Binder
series 713/763
0.6 x 3.5 mm
Potential equalization
PZ2
Cable glands (F16 plastic housing)
SW25
Cable glands (F15 stainless steel housing, F34 aluminium housing and
optional Harting HAN8D plug connector)
SW22
Cable gland (optional M12 plug connector, Binder series 713/763)
SW13
Crimp contacts optional Harting HAN8D plug connector
Suitable crimping tool
6�1�2
Connecting cable requirements
The connecting cables provided by the customer must fulfil the following requirements:
• Electrical safety in accordance with applicable national regulations.
• Permitted temperature range → 55
• Normal installation cable with at least three wires
• Cable cross-sections: 0.2 to 2.5 mm
2
or AWG 24 to 12
• The terminals are only approved for connecting fixed cables. The operator must provide
suitable strain relief.