Solimotion FTR20
Commissioning
Hauser
29
8�3�1
Calibration with movement of bulk solids
The automatic calibration with movement of bulk solids (
Function 1
) is adequate for most
applications. If the bulk solids movement after an automatic calibration is not detected as
desired, you can adjust the Solimotion to the application manually using an additional manual
calibration.
Set encoding switch to Position 1
→ Display of the function number
After 2 seconds: Display of the current signal strength, example:
Simultaneously press the and
keys on the device with maximum solid flow
→ Automatic calibration is carried out
→ Display of the signal strength with maximum solid flow
Move the encoding switch to the initial position 0
→ Display of the current signal strength
Optional: Additional manual calibration with movement of bulk solids (Function 3)
Using the manual calibration, which is ideally carried out after the automatic calibration, the
Solimotion can be adapted to the application manually if necessary.
Move the encoding switch to position 3
→ Display of the function number
After 2 seconds: Display of the current signal strength, example:
Press the or key on the device to achieve an increase or reduction of the signal
strength with maximum solid flow
→ Display of the signal strength with maximum solid flow (all 10 LEDs illuminate)
Move the encoding switch to the initial position 0
→ Display of the current signal strength
• The Solimotion FTR20 is calibrated if,
a) for moving bulk solids, the switch point (LED 5) of the switch output is exceeded reliably.
b) For the current output, only one or two (minimum solid flow) or at least six LEDs
(maximum solid flow) are illuminated.
• A repeated automatic calibration (function 1 or function 2) resets any calibration carried out
earlier.