Modbus RS485 Register Information
Proline Cubemass 300 Modbus RS485
262
Hauser
"Partial pipe det" submenu
Navigation: Expert → Sensor → Process param. → Partial pipe det
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Assign variable (1860)
5106
Integer
Read / Write
0 = Off
4 = Density
5 = Ref.density
Low value (1861)
5110 to 5111
Float
Read / Write
Signed floating-point number
High value (1858)
5112 to 5113
Float
Read / Write
Signed floating-point number
Response time (1859)
5108 to 5109
Float
Read / Write
0 to 100 s
Max. damping (6040)
2414 to 2415
Float
Read / Write
Positive floating-point number
"Measurement mode" submenu
Navigation: Expert → Sensor → Measurement mode
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Select medium (6062)
2442
Integer
Read / Write
0 = Liquid
1 = Gas
Select gas type (6074)
5229
Integer
Read / Write
0 = Air
1 = Nitrogen N2
2 = Argon Ar
3 = Helium He
4 = Carbon diox. CO2
5 = Oxygen O2
6 = Methane CH4
7 = Ammonia NH3
9 = Hydrogen H2
10 = Ethane C2H6
11 = Propane C3H8
12 = Butane C4H10
13 = Chlorine Cl2
14 = Hydrog.chlor.HCl
15 = Carbon monox. CO
16 = Nitrous ox. N2O
17 = Nitrog. ox. NOx
18 = Hydrog.sulf. H2S
19 = Sulf. hex.fl.SF6
20 = Propylene C3H6
21 = Ozone O3
22 = Others
23 = Ethylene C2H4
Sound velocity (6147)
7413 to 7414
Float
Read / Write
1 to 99
999.9999 m/s
Temp. coeff. SV (6181)
7411 to 7412
Float
Read / Write
Positive floating-point number
"External comp." submenu
Navigation: Expert → Sensor → External comp.
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Pressure compen. (6130)
5184
Integer
Read / Write
0 = Off
1 = Fixed value
2 = External value
11 = Current input 1
12 = Current input 2
Pressure value (6059)
5185 to 5186
Float
Read / Write
Positive floating-point number
External press. (6209)
2440 to 2441
Float
Read / Write
Positive floating-point number