Proline Cubemass 300 Modbus RS485
Description of device parameters
Hauser
153
Switch-on value
Navigation
Expert → Output → Relay output 1 to n → Switch-on value (0810–1 to n)
Prerequisite
In the
Relay outp.func.
parameter (→ 149), the
Limit
option is selected.
Description
Use this function to enter the measured value for the switch-on point.
User entry
Signed floating-point number
Factory setting
Country-specific:
• 0 kg/h
• 0 lb/min
Additional information
Description
Use this function to enter the limit value for the switch-on value (process variable >
switch-on value = closed, conductive).
When using a hysteresis: Switch-on value > Switch-off value.
Dependency
The unit is dependent on the process variable selected in the
Assign limit
parameter
Switch-on delay
Navigation
Expert → Output → Relay output 1 to n → Switch-on delay (0814–1 to n)
Prerequisite
In the
Relay outp.func.
parameter (→ 149), the
Limit
option is selected.
Description
Use this function to enter a delay time for switching on the switch output.
User entry
0.0 to 100.0 s
Factory setting
0.0 s
Failure mode
Navigation
Expert → Output → Relay output 1 to n → Failure mode (0811–1 to n)
Description
Use this function to select the failure mode of the relay output in the event of a device
alarm.
Selection
• Actual status
• Open
• Closed
Factory setting
Open