Description of device parameters
Proline Cubemass 300 Modbus RS485
120
Hauser
Damping out. 1 to n
Navigation
Expert → Output → Curr.output 1 to n → Damping out. 1 to n (0363–1 to n)
Prerequisite
One of the following options is selected in the
Assign curr.
• Mass flow
• Volume flow
• Correct.vol.flow
• Target mass flow
• Carrier mass fl.
• Density
• Ref.density
• Concentration
• Temperature
• Carr. pipe temp.
• Electronic temp.
• Osc. freq. 0
• Osc. ampl. 0
• Freq. fluct. 0
• Osc. damping 0
• Osc.damp.fluct 0
• Signal asymmetry
• Exc. current 0
Detailed description of the options
Oscil. frequency, Oscil. amplitude, Oscil.
damping
and
Signal asymmetry
:
Value 1 display
One of the following options is selected in the
Current span
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• 0...20 mA
Description
Use this function to enter a time constant for the reaction time of the current output signal
to fluctuations in the measured value caused by process conditions.
User entry
0.0 to 999.9 s
Factory setting
1.0 s
Additional information
Entry
Use this function to enter a time constant (PT1 element
) for current output damping:
• If a low time constant is entered, the current output reacts particularly quickly to
fluctuating measured variables.
• On the other hand, the current output reacts more slowly if a high time constant is
entered.
Damping is switched off if
0
is entered (factory setting).
*
Visibility depends on order options or device settings
6)
proportional transmission behavior with first order delay