Modbus RS485 Register Information
Proline Cubemass 300 Modbus RS485
266
Hauser
6.3.5
"Output" submenu
"Curr.output 1 to n" submenu
Navigation: Expert → Output → Curr.output 1 to n
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Terminal no. (0379–1 to n)
1: 6545
2: 6546
3: 6547
Integer
Read
0 = Not used
2 = 24-25 (I/O 2)
3 = 22-23 (I/O 3)
Signal mode (0377–1 to n)
1: 6421
2: 6422
3: 6423
Integer
Read / Write
0 = Passive
2 = Active
Assign curr. 1 to n (0359–1 to n)
1: 5927
2: 5928
3: 5929
Integer
Read / Write
0 = Off
1 = Mass flow
2 = Volume flow
3 = Correct.vol.flow
4 = Density
5 = Ref.density
7 = Temperature
8 = Osc. ampl. 0
9 = Signal asymmetry
23 = Carr. pipe temp.
32 = Exc. current 0
39 = Electronic temp.
48 = Osc. freq. 0
63 = Osc. damping 0
66 = Pressure
67 = Osc.damp.fluct 0
68 = Freq. fluct. 0
73 = Concentration
74 = Target mass flow
75 = Carrier mass fl.
78 = Carrier vol. fl.
79 = Carr.corr.vol.fl
83 = Oil density
84 = Water density
86 = GSV flow
87 = GSVa
88 = Oil mass flow
89 = Water mass flow
90 = NSV flow
91 = NSVa
92 = S&W volume flow
93 = Ref.dens.altern.
94 = Oil corr.vol.fl.
95 = Water corr.v.fl.
96 = Targ.corr.vol.fl
97 = Target vol. flow
99 = Oil volume flow
101 = Water cut
102 = Water vol. flow
Current span (0353–1 to n)
1: 5923
2: 5924
3: 5925
Integer
Read / Write
0 = 4...20 mA
1 = 4...20 mA US
2 = 4...20 mA NAMUR
3 = 0...20 mA
4 = Fixed current
Fixed current (0365–1 to n)
1: 5987 to 5988
2: 5989 to 5990
3: 5991 to 5992
Float
Read / Write
0 to 22.5 mA
0/4 mA value (0367–1 to n)
1: 6195 to 6196
2: 6197 to 6198
3: 6199 to 6200
Float
Read / Write
Signed floating-point number