Diagnostics and troubleshooting
iTHERM TrustSens TM371, TM372
38
Hauser
Diagnostic
number
Priority
Short text
Remedy
Status
signal
(factory
default)
Configurable
Diagnostic
behavior
from the
factory
Configurable
Not
configurable
Not
configurable
401
15
Factory reset active
Factory reset in progress, please
wait.
C
Warning
402
16
Initialization active
Initialization in progress, please
wait.
C
Warning
410
3
Data transfer failed
1. Check connection.
2. Repeat data transfer.
F
Alarm
411
17
Up-/download active
Up-/download in progress, please
wait.
C
Warning
435
5
Linearization faulty
Check linearization.
F
Alarm
437
4
Configuration
incompatible
Execute factory reset.
F
Alarm
438
30
Dataset different
1. Check data set file.
2. Check device parameterization.
3. Download new device
parameterization.
M
Warning
485
18
Process variable
simulation active-
Sensor
Deactivate simulation.
C
Warning
491
19
Output simulation -
current output
Deactivate simulation.
C
Warning
495
20
Diagnostic event
simulation active
Deactivate simulation.
C
Warning
501
6
Wiring error
Check wiring.
F
Alarm
531
6
Factory adjustment
missing
1. Contact service organization.
2. Replace device.
F
Alarm
8
Factory adjustment
missing-Sensor
9
Factory adjustment
missing-Reference
sensor
10
Factory adjustment
missing-Current
output
537
11
Configuration
1. Check device configuration
2. Up- and download new
configuration
F
Alarm
12
Configuration-Sensor
1. Check sensor configuration.
2. Check device configuration.
13
Configuration-
Reference sensor
14
Configuration-Current
output
1. Check application
2. Check the current output
parameterization
801
23
Supply voltage too low Increase supply voltage.
S
Alarm
825
24
Operating
temperature
1. Check ambient temperature.
2. Check process temperature.
S
Warning