Operating menu and parameter description
iTHERM TrustSens TM371, TM372
96
Hauser
Failure current
Navigation
Expert → Output → Failure current
Prerequisite
The option
High alarm
is enabled in the failure mode.
Description
Use this function to set the value the current output adopts in an alarm condition.
User entry
21.5 to 23 mA
Factory setting
22.5
Adjustment of the analog output (4 and 20 mA current trimming)
Current trimming is used to compensate the analog output (D/A conversion). Here, the
output current of the transmitter must be adapted so that it suits the value expected at the
higher-order system.
Current trimming does not affect the digital HART
®
value. This can cause the
measured value shown on a locally installed display to differ from the value displayed
in the higher-order system.
Procedure
1. Start
ß
2. Install an accurate amperemeter (more accurate then the transmitter) in the current loop.
ß
3. Switch on current output simulation and set the simulation value to 4 mA.
ß
4. Measure the loop current with the amperemeter and make a note of the value.
ß
5. Set the simulation value to 20 mA.
ß
6. Measure the loop current with the amperemeter and make a note of the value.
ß
7. Enter the current values determined as adjustment values in the
Current trimming 4 mA / 20 mA
parameters
ß
8. End
Current trimming 4 mA
Navigation
Expert → Output → Current trimming 4 mA
Description
Use this function to set the correction value for the current output at the start of the
measuring range at 4 mA.