Description of device parameters
Deltabar FMD71, FMD72
60
Description
Displays the lowest pressure value measured (peakhold indicator). You can reset this
indicator by means of the "Reset peakhold" parameter.
COUNTER P < Pmin (267)
Navigation
Expert → Diagnosis → Sensor LP → Counter P < Pmin (267)
Write permission
No write permissions. Parameter is read only.
Description
Displays the negative pressure counter for the respective sensor module. The counter is
incremented each time error 841 occurs. You can reset this value using the "Reset Peakhold
(161)" parameter.
Max. meas. press. (268)
Navigation
Expert → Diagnosis → Sensor LP → Maximum Pressure (268)
Write permission
No write permissions. Parameter is read only.
Description
Displays the highest pressure value measured (peakhold indicator). You can reset this peak
indicator via the "Reset peakhold (161)" parameter.
COUNTER P > Pmax (269)
Navigation
Expert → Diagnosis → Sensor LP → Counter P > Pmax (269)
Write permission
No write permissions. Parameter is read only.
Description
Displays the overpressure counter for the respective sensor module. The limit value is:
upper sensor module nominal value + 10% of upper sensor module nominal value. You can
reset this value using the "Reset Peakhold (161)" parameter.
MIN. MEAS. TEMP. (270)
Navigation
Expert → Diagnosis → Sensor LP → Min. Meas.Temp. (270)
Write permission
No write permissions. Parameter is read only.
Description
Displays the smallest temperature measured in the sensor module. You can reset this value
using the "Reset Peakhold (161)" parameter.