Deltabar FMD71, FMD72
Description of device parameters
31
Navigation
Expert → Measurement → Level → Empty Pressure (029)/(185)
Write permission
Operators/Service engineers/Expert
Description
Enter the pressure value for the lower calibration point (vessel empty). See also "Empty
Calib. (028)".
Prerequisite
• "Level Selection" = In pressure
• "Calibration mode" = Dry -> entry
• "Calibration mode" = Wet -> display
Factory setting
0.0
Empty height (030)/(186)
Navigation
Expert → Measurement → Level → Empty Height (030)/(186)
Write permission
Operators/Service engineers/Expert
Description
Enter the height value for the lower calibration point (vessel empty). The unit is selected
via the "Height unit (026)" parameter.
Prerequisite
• "Level Selection" = "In height"
• "Calibration mode" = Dry -> entry
• "Calibration mode" = Wet -> display
Factory setting
0.0
Full Calib. (031)/(012)
Navigation
Expert → Measurement → Level → Full Calib. (031)/(012)
Write permission
Operators/Service engineers/Expert
Description
Enter the output value for the upper calibration point (vessel full). The unit defined in "Unit
Before Lin." must be used.
Note
• In the case of wet calibration, the level (vessel full) must actually be available. The
associated pressure is then automatically recorded by the device.
• In the case of dry calibration, the level (vessel full) does not have to be available. The
associated pressure has to be entered in the "Full Pressure" parameter for the "In pressure"
level selection. The associated height has to be entered in the "Full height" parameter for
the "In height" level selection.
Factory setting
100.0
Full Pressure (032)/(187)
Summary of Contents for Deltabar FMD71
Page 2: ......