Options
• In pressure
If this option is selected, specify two pressure/level value pairs. The level value is
displayed directly in the unit that you select via the "Unit Before Lin." parameter.
• In height
If this option is selected, specify two height/level value pairs. From the measured
pressure, the device first calculates the height using the density. This information is then
used to calculate the level in the "Unit Before Lin." selected using the two value pairs
specified.
Factory setting
In pressure
Unit before lin. (025)
Navigation
Expert → Measurement → Level → Level Before Lin. (025)
Write permission
Operators/Service engineers/Expert
Description
Select the unit for the measured value display for the level before linearization.
Example
• Current measured value: 0.3 ft
• New output unit: m
• New measured value: 0.3 m
Options
• %
• mm, cm, dm, m
• ft, in
• m
3
, in
3
• l, hl
• ft
3
• gal, Igal
• kg, t
• lb
Note
The unit selected is only used to describe the measured value. This means that when
selecting a new output unit, the measured value is not converted.
Factory setting
%
Height unit (026)
Navigation
Expert → Measurement → Level → Height Unit (026)
Write permission
Operators/Service engineers/Expert
Description
Select the height unit. The measured pressure is converted to the selected height unit
using the "Adjust Density" parameter.
Prerequisite
"Level Selection" = "In height"