Deltabar FMD71, FMD72
Description of device parameters
33
Description
Enter a new density value for density correction. The calibration was carried out with the
medium water, for example. Now the vessel is to be used for another medium with
another density. The calibration is corrected appropriately by entering the new density
value in the "Process Density" parameter.
Note
If you change to dry calibration after completing a wet calibration using the "Calibration
mode" parameter, the density for the "Adjust Density" and "Process Density" parameters
must be entered correctly before changing the calibration mode.
Factory setting
1.0
Lin. mode (037)
Navigation
Expert → Measurement → Linearization → Lin. Mode (037)
Write permission
Operators/Service engineers/Expert
Description
Select the linearization mode.
Options
• Linear
The level is output without being converted beforehand. "Level before Lin" is output.
• Erase table
The existing linearization table is deleted.
• Manual entry (sets the table to edit mode, an alarm is output):
The value pairs of the table (X-value (193/040) and Y-val. (041)) are entered manually.
• Semi-automatic entry (sets the table to edit mode, an alarm is output):
The vessel is emptied or filled in stages in this entry mode. The device automatically
records the level value (X-value (193/040)). The associated volume, mass or % value is
entered manually (Y-val (041)).
• Activate table
The table entered is activated and checked with this option. The device shows the level
after linearization.
Factory setting
Linear
Unit after lin. (038)
Navigation
Expert → Measurement → Linearization → Unit After Lin. (038)
Write permission
Operators/Service engineers/Expert
Description
Select volume unit, mass, height or % (unit of the Y-val).
Summary of Contents for Deltabar FMD71
Page 2: ......