Description of device parameters
Deltabar FMD71, FMD72
34
Options
• %
• cm, dm, m, mm
• hl
• in
3
, ft
3
, m
3
,
• l
• in, ft
• kg, t
• lb
• gal
• Igal
Factory setting
%
Line numb. (039)
Navigation
Expert → Measurement → Linearization → Line-numb. (039)
Write permission
Operators/Service engineers/Expert
Description
Enter the number of the current point in the table. The subsequent entries in "X-val." and
"Y-val." refer to this point.
Input range
1...32
X-value (040)/(123)/(193)
Navigation
Expert → Measurement → Linearization → X-value (040)/(123)/(193)
Write permission
Operators/Service engineers/Expert
Description
Enter the X-value (level before linearization) for the specific point in the table and confirm.
Note
• If "Lin. mode" = "Manual", the level value must be entered.
• If "Lin. mode" = "Semiautomatic", the level value is displayed and has to be confirmed by
entering the paired Y-val.
Y-val (041)/(194)
Navigation
Expert → Measurement → Linearization → Y-val (041)/(194)
Write permission
Operators/Service engineers/Expert
Description
Enter the Y-val (value after linearization) for the specific point in the table. The unit is
determined by "Unit after lin."
Note
The linearization table must be monotonic (increasing or decreasing).
Summary of Contents for Deltabar FMD71
Page 2: ......