8
Block
Errors
7.12.5
Block Errors
lists conditions reported in the BLOCK_ERR parameter. Conditions in italics
are inactive for the PID block and are given here only for your reference.
Table 7-28 BLOCK _ERR Conditions
Condition
Number
Condition Name and Description
0
Other
1
Block Configuration Error: The BY_PASS parameter is not configured and is set to 0, the SP_HI_LIM
is less than the SP_LO_LIM, or the OUT_HI_LIM is less than the OUT_LO_LIM.
2
Link Configuration Error
3
Simulate Active
4
Local Override: The actual mode is LO.
5
Device Fault State Set
6
Device Needs Maintenance Soon
7
Input Failure/Process Variable has Bad Status: The parameter linked to IN is indicating a Bad status.
8
Output Failure
9
Memory Failure
10
Lost Static Data
11
Lost NV Data
12
Readback Check Failed
13
Device Needs Maintenance Now
14
Power Up
15
Out of Service: The actual mode is out of service.
7.12.6
Modes
The PID function block supports the following modes:
•
Manual (Man)—The block output (OUT) may be set manually.
•
Automatic (Auto)—The SP may be set manually and the block algorithm calculates OUT.
•
Cascade (Cas)—The SP is calculated in another block and is provided to the PID block
through the CAS_IN connection.
•
RemoteCascade (RCas)—The SP is provided by a host computer that writes to the
RCAS_IN parameter.
•
RemoteOutput (Rout)—The OUT is provided by a host computer that writes to the
ROUT_IN parameter.
•
Local Override (LO)—The track function is active. OUT is set by TRK_VAL. The
BLOCK_ERR parameter shows Local override.
•
Initialization Manual (IMan)—The output path is not complete (for example, the
cascade-to-slave path might not be open). In IMan mode, OUT tracks BKCAL_IN.
•
Out of Service (O/S)—The block is not processed. The OUT status is set to Bad: Out of
Service. The BLOCK_ERR parameter shows Out of service.
You can configure the Man, Auto, Cas, and O/S modes as permitted modes for operator entry.
Summary of Contents for Rosemount OCX 8800
Page 2: ......
Page 41: ...Instruction Manual IM 106 880C OI Section 2 Installation April 2017 Section contents 17 ...
Page 205: ...Alarm Relay Events April 2017 Instruction Manual IM 106 880C OI 17 8 Alarm Relay Events ...
Page 251: ...Replace Tube Fittings April 2017 Instruction Manual IM 106 880C OI 22 4 Install Tube Fittings ...
Page 261: ...Instruction Manual IM 106 880C OI Safety Data April 2017 Appendix contents 233 ...
Page 263: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 235 ...
Page 267: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 239 ...
Page 271: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 243 ...
Page 273: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 245 ...
Page 275: ...Instruction Manual Safety Data IM 106 880C OI April 2017 IMPORTANT Safety Instructions 247 ...
Page 277: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 249 ...
Page 279: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 251 ...
Page 300: ...Instruction Manual IM 106 880C OI Index April 2017 Manual index 27 4 ...
Page 304: ...Index April 2017 Instruction Manual IM 106 880C OI 27 8 Manual index ...
Page 305: ......