Pressure Transmitter used to Measure Level in an Open
Tank
Situation #2
The transmitter in situation #1 is installed below the tank in a position where the liquid column
in the impulse line, when the tank is empty, is equivalent to 2.0 psi (
Figure 7-11 Situation #2 Diagram
Solution
lists the appropriate configuration settings.
Table 7-24 Analog Input Function Diagram for a Pressure Transmitter used in Level Measurement
(Situation #2
Parameter
Configured Values
L_TYPE
Indirect
XD_SCALE
2 to 9 psi
OUT_SCALE
0 to 16 ft
Summary of Contents for Rosemount OCX 8800
Page 2: ......
Page 41: ...Instruction Manual IM 106 880C OI Section 2 Installation April 2017 Section contents 17 ...
Page 205: ...Alarm Relay Events April 2017 Instruction Manual IM 106 880C OI 17 8 Alarm Relay Events ...
Page 251: ...Replace Tube Fittings April 2017 Instruction Manual IM 106 880C OI 22 4 Install Tube Fittings ...
Page 261: ...Instruction Manual IM 106 880C OI Safety Data April 2017 Appendix contents 233 ...
Page 263: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 235 ...
Page 267: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 239 ...
Page 271: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 243 ...
Page 273: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 245 ...
Page 275: ...Instruction Manual Safety Data IM 106 880C OI April 2017 IMPORTANT Safety Instructions 247 ...
Page 277: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 249 ...
Page 279: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 251 ...
Page 300: ...Instruction Manual IM 106 880C OI Index April 2017 Manual index 27 4 ...
Page 304: ...Index April 2017 Instruction Manual IM 106 880C OI 27 8 Manual index ...
Page 305: ......