The Analog Input (AI) function block processes field device measurements and makes them
available to other function blocks. The output value from the AI block is in engineering units and
contains a status indicating the quality of the measurement. The measuring device may have
several measurements or derived values available in different channels. Use the channel number
to define the variable that the AI block processes.
The AI block supports alarming, signal scaling, signal filtering, signal status calculation, mode
control, and simulation. In Automatic mode, the block’s output parameter (OUT) reflects the
process variable (PV) value and status. In Manual mode, OUT may be set manually. The Manual
mode is reflected on the output status. A discrete output (OUT_D) is provided to indicate
whether a selected alarm condition is active. Alarm detection is based on the OUT value and
user specified alarm limits.
lists the AI block parameters and their units of
measure, descriptions, and index numbers.
Table 7-20 Definitions of Analog Input Function Block System Parameters
ACK_OPTION
23
None
Used to set auto acknowledgment of alarms.
ALARM_HYS
24
Percent
The amount the alarm value must return within the alarm limit before
the associated active alarm condition clears.
ALARM_SEL
38
None
Used to select the process alarm conditions that will cause the OUT_D
parameter to be set.
ALARM_SUM
22
None
The summary alarm is used for all process alarms in the block. The
cause of the alert is entered in the subcode field. The first alert to be-
come active will set the Active status in the Status parameter. As soon
as the Unreported status is cleared by the alert reporting task, another
block alert may be reported without clearing the Active status, if the
subcode has changed.
ALERT_KEY
04
None
The identification number of the plant unit. This information may be
used in the host for sorting alarms, etc.
BLOCK_ALM
21
None
The block alarm is used for all configuration, hardware, connection
failure or system problems in the block. The cause of the alert is
entered in the subcode field. The first alert to become active will set
the Active status in the Status parameter. As soon as the Unreported
status is cleared by the alert reporting task, another block alert may be
reported without clearing the Active status, if the subcode has
changed.
BLOCK_ERR
06
None
This parameter reflects the error status associated with the hardware or
software components associated with a block. It is a bit string, so that
multiple errors may be shown.
CHANNEL
15
None
The CHANNEL value is used to select the measurement value. Refer to
the appropriate device manual for information about the specific chan-
nels available in each device.
You must configure the CHANNEL parameter before you can configure
the XD_SCALE parameter.
FIELD_VAL
19
Percent
The value and status from the transducer block or from the simulated
input when simulation is enabled.
GRANT_DENY
12
None
Options for controlling access of host computers and local control pan-
els to operating, tuning, and alarm parameters of the block. Not used
by device.
HI_ALM
34
None
The HI alarm data, which includes a value of the alarm, a timestamp of
occurrence and the state of the alarm.
HI_HI_ALM
33
None
The HI HI alarm data, which includes a value of the alarm, a timestamp
of occurrence and the state of the alarm.
Introduction
115
Parameter
Index
Number Units
Description
Summary of Contents for Rosemount OCX 8800
Page 2: ......
Page 41: ...Instruction Manual IM 106 880C OI Section 2 Installation April 2017 Section contents 17 ...
Page 205: ...Alarm Relay Events April 2017 Instruction Manual IM 106 880C OI 17 8 Alarm Relay Events ...
Page 251: ...Replace Tube Fittings April 2017 Instruction Manual IM 106 880C OI 22 4 Install Tube Fittings ...
Page 261: ...Instruction Manual IM 106 880C OI Safety Data April 2017 Appendix contents 233 ...
Page 263: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 235 ...
Page 267: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 239 ...
Page 271: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 243 ...
Page 273: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 245 ...
Page 275: ...Instruction Manual Safety Data IM 106 880C OI April 2017 IMPORTANT Safety Instructions 247 ...
Page 277: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 249 ...
Page 279: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 251 ...
Page 300: ...Instruction Manual IM 106 880C OI Index April 2017 Manual index 27 4 ...
Page 304: ...Index April 2017 Instruction Manual IM 106 880C OI 27 8 Manual index ...
Page 305: ......