Parameter
05.035
Auto-switching Frequency Change
Short description
Defines auto-switching frequency control with thermal model
Mode
Open
‑
Loop
Minimum
0
Maximum
2
Default
0
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, TE
Value
Text
0
Enabled
1
Disabled
2
No Ripple Detect
The drive inverter can be damaged if the temperature is too high. The inverter can also be damaged or the lifetime of the power devices reduced, if the temperature ripple of the devices is too high.
Auto-switching Frequency Change
(05.035) defines the action taken if the drive inverter becomes too hot or the temperature ripple becomes too high.
Enabled:
If the inverter becomes too hot or the ripple temperature is higher than the level defined by
Maximum Inverter Temperature Ripple
(05.039) the switching frequency is reduced in an attempt to prevent tripping.
Disabled:
The switching frequency is not reduced, and so the drive will trip if the inverter is too hot or the temperature ripple is too high.
No Ripple Detect:
The switching frequency is reduced if the inverter temperature, but not the temperature ripple is too high. If the temperature ripple exceeds the level defined by
Maximum Inverter Temperature Ripple
(05.039) then the drive will trip.
The switching frequency is changed in steps defined by
Auto-switching Frequency Step Size
(05.036). For example with a switching frequency of 16kHz and a step size of two, the frequency will be reduced to 8kHz, then 4kHz etc.
Minimum Switching Frequency
(05.038) defines the minimum switching frequency that the system will attempt to use. If the switching frequency needs to switch to a lower level, then the drive will trip.
If
Minimum Switching Frequency
is changed the new value will only become active when
Switching Frequency
is at or above the minimum value.
Parameter
05.036
Auto-switching Frequency Step Size
Short description
Auto-switching frequency redcution step size
Mode
Open
‑
Loop
Minimum
1
Maximum
2
Default
2
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW
See
Auto-switching Frequency Change
(05.035).
Parameter
05.037
Switching Frequency
Short description
Displays the current switching frequency used by the drive
Mode
Open
‑
Loop
Minimum
0
Maximum
6
Default
Units
kHz
Type
8 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, TE, ND, NC, PT
Value
Text
0
2
1
3
2
4
3
6
4
8
5
12
6
16
Shows the actual inverter switching frequency after the auto-change function.
Parameter
05.038
Minimum Switching Frequency
Short description
Minuimum Switching Frequency
Mode
Open
‑
Loop
Minimum
0
Maximum
VM_MIN_SWITCHING_FREQUENCY
Default
0
Units
kHz
Type
8 Bit User Save
Update Rate
Background Read
Display Format
Standard
Decimal Places
0
Coding
RW, TE, VM
Value
Text
0
2
1
3
2
4
3
6
4
8
5
12
6
16
See
Auto-switching Frequency Change
(05.035).
Parameter
05.039
Maximum Inverter Temperature Ripple
Short description
Maximum Inverter Temperature Ripple
Mode
Open
‑
Loop
Minimum
20
Maximum
60
Default
60
Units
°C
Type
8 Bit User Save
Update Rate
Background Read
Display Format
Standard
Decimal Places
0
Coding
RW
Maximum Inverter Temperature Ripple
(05.039) defines the maximum inverter temperature ripple allowed before the switching frequency is reduced. See
Auto-switching Frequency Change
(05.035).
Parameter
05.040
Spin Start Boost
Short description
Defines the level of spin start boost used by the algorithm that detects the speed of a spinning motor
Mode
Open
‑
Loop
Minimum
0.0
Maximum
10.0
Default
1.0
Units
Type
8 Bit User Save
Update Rate
Background Read
Display Format
Standard
Decimal Places
1
Coding
RW
Spin Start Boost
(05.040) is used by the algorithm that detects the speed of a spinning motor when the drive is enabled and
Catch A Spinning Motor
(06.009) ≥ 1. For most motors
Spin Start Boost
(05.040) does not need to be changed
from the default value, but for some larger motors
Spin Start Boost
(05.040) may need to be increased. If
Spin Start Boost
(05.040) is too small the drive will detect zero speed whatever the speed of the motor, and if
Spin Start Boost
(05.040) is too large the motor may accelerate away from standstill when the drive is enabled.
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
75
Summary of Contents for Powerdrive F300
Page 1: ...Parameter Reference Guide Powerdrive F300 Open Loop Mode Issue 01 15 00 ...
Page 21: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 21 ...
Page 112: ...112 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Page 144: ...144 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Page 231: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 231 ...
Page 232: ...232 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...