1. Security must be unlocked.
2. The
User Security Code
(11.030) should be set to zero. For security to remain cleared after power down then a parameter save should
be performed.
At any time
Security Status
(11.085) can be changed between 0 and 1 to restrict access to Menu 0 alone or to all menus. If the change is made by a
keypad the new value becomes active on leaving parameter edit mode.
It should be that
Security Status
(11.085) is a volatile parameter and that the actual state of the security system is stored in
Security Status
(11.085) and
Menu Access Status
(11.086), which are both power-down save parameters. Therefore the security status will be stored when the drive goes into the
under-voltage state. If the drive is already in the under-voltage state the security state should be saved by writing 1001 to
Parameter mm.000
(mm.000)
and initiating a reset.
Parameter
11.046
Defaults Previously Loaded
Short description
Displays the defaults previously loaded in the drive
Mode
Open
‑
Loop
Minimum
0
Maximum
2000
Default
Units
Type
16 Bit User Save
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Defaults Previously Loaded
(11.046) shows the value used to load the previously loaded defaults (i.e. 1233 for 50Hz defaults, or 1244 for 60Hz
defaults).
Parameter
11.047
Onboard User Program: Enable
Short description
Enables the onboard user program
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
1
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, TE
Value
Text
0
Stop
1
Run
Onboard user programming provided a background task that loops continuously and a timed task that is executed each time at a defined rate.
Onboard User Program: Enable
(11.047) allows the onboard user program to the stopped or run.
0: Stop
The onboard user program is stopped. If it is restarted by setting
Onboard User Program: Enable
(11.047) to a non-zero value the background task
starts from the beginning.
1: Run
The onboard user program will run.
Parameter
11.048
Onboard User Program: Status
Short description
Displays the status of the onboard user program
Mode
Open
‑
Loop
Minimum
-2147483648
Maximum
2147483647
Default
Units
Type
32 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Onboard User Program: Status
(11.048) shows the status of the onboard user program.
Value
Description
0
A user program is present but is stopped
1
The user program is running
2
The user program has an exception
3
No user program is present
208
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
Summary of Contents for Powerdrive F300
Page 1: ...Parameter Reference Guide Powerdrive F300 Open Loop Mode Issue 01 15 00 ...
Page 21: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 21 ...
Page 112: ...112 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Page 144: ...144 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Page 231: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 231 ...
Page 232: ...232 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...